Descargar Imprimir esta página

VALPES ER PLUS Manual De Instalación Y Funcionamiento página 26

Ocultar thumbs Ver también para ER PLUS:

Publicidad

Idiomas disponibles

Idiomas disponibles

POWER SUPPLY : 3P+T DIN43650 CONNECTOR
N
-
TP/PE
1
2
3
1
2
3
1
15V-30V 50/60Hz (12V-48V DC)
100V-240V 50/60Hz (100V-350V DC)
TP/PE
17
18
17
18
P6
POSI
13
14
+
FEEDBACK
SIGNAL
0-20mA / 4-20mA / 0-10V
The card resolution is 1°
10 kOhm input impedance if control with voltage (0-10V)
100 Ohm input impedance if control with current (0-20mA ou 4-20mA)

The control voltage must be S.E.L.V. (Safety Extra Low Voltage).

The terminal temperature can reach 90°C.

The feedback must be connect with rigid wires. If the applied voltage is higher than 42V, the user must foresee a
fuse in the power supply line.

For a use with a long power supply wiring, the induction current generated by the wires mustn't be higher than 1mA.

The used wires must be rigid
26
Ph
+
2
3
D1
D2
A
C
15
16
+
SETPOINT
SIGNAL
r
~
+
~
A
B
Motor
=
REP
DESIGNATION
FC0
Open limit switch
FCF
Close limit switch
FC1
Auxiliary limit switch 1
FC2
Auxiliary limit switch 2
D1/D2 Failure report Terminal strip (24V DC / 3A max)
EN
FEEDBACK
4
5
6
7
8
SNAA690000
DSBA3200 • Rév. 21/02/2022
9

Publicidad

loading

Este manual también es adecuado para:

Er plus serieEr10 plusEr20 plusEr35 plusEr60 plusEr100 plus