Descargar Imprimir esta página

Parameter Selection Sequence - VALPES ER PLUS Manual De Instalación Y Funcionamiento

Ocultar thumbs Ver también para ER PLUS:

Publicidad

Idiomas disponibles

Idiomas disponibles

EN

PARAMETER SELECTION SEQUENCE

1 K1, K2 and K3 shunts positioning
Position the shunts as follows (before modification, switch off the card):
K3 OFF
K3 ON
2 Selection of the flow direction of the valve
2.1 Normal flow direction (by default)
G
2.2 Inverse flow direction
R
3 Selection of the type of input control signal
3.1 Voltage control signal 0-10V
R
3.2 Current control signal 4-20mA (by default)
R
3.3 Current control signal 0-20mA
R
4 Learning mode
G
R
R
R
G
G
NORMAL OPERATING MODE
G
In the case of an over torque, the motor stops and the 2 LEDS lights then together to indicate the
action of the torque limiter. To re-start it, you must either reverse the sense of rotation, either switch
G
R
the power off and on.
DSBA3200 • Rév. 21/02/2022
Setpoint
signal
0-10V
0-10V
0-10V
0-20mA
0-20mA
0-20mA
4-20mA
4-20mA
4-20mA
Press the OPEN button and apply the operating voltage to the card while keeping this button

pressed.
The green LED lights up. Release the OPEN button.

Disconnect the card.

Press the CLOSE button and apply the operating voltage to the card while keeping this button

pressed.
The red LED lights up. Release the CLOSE button.

Disconnect the card.

Press the MEM button and apply the operating voltage to the card while keeping this button

pressed.
The red LED will light up 3 times. Release this button.

Disconnect the card.

Press the MEM and CLOSE buttons and apply the operating voltage to the card while keeping

these buttons pressed.
The red LED will light up 3 times. Release these buttons.

Disconnect the card.

Press the MEM and OPEN buttons and apply the operating voltage to the card while keeping

these buttons pressed.
The red LED will light up 3 times. Release these buttons.

Disconnect the card.

Press the OPEN and CLOSE buttons and apply the operating voltage to the card while

keeping these buttons pressed.
The 2 LEDs will light up. Release these buttons and the 2 LEDs will run out. The card is now in

the learning mode.
Press the CLOSE button to put the valve in its closed position. The red LED will light up.

Store this selected closed position by pushing MEM + CLOSE, the red LED will light up 2

times as a confirmation of acknowledgement.
Press the OPEN button to put the valve in its open position. The green LED will light up.

Store this selected open position by pushing MEM + OPEN, the green LED will light up 2

times as a confirmation of acknowledgement.

Now, the positions selected have been stored. Disconnect the card.
Apply the operating voltage to the card. The green LED will light up 3 times.

Under normal operating conditions, the green LED will light up when the drive motor opens the

valve, and the red LED will light up when the drive motor closes it.
If both LEDs remain ran out, it means that the drive motor has not been triggered.

Shunt K1
Feedback
signal
A
B
0-10V
ON OFF
0-20mA
ON OFF
4-20mA
ON OFF
0-10V
OFF
ON
0-20mA
OFF
ON OFF
4-20mA
OFF
ON OFF
0-10v
OFF
ON
0-20mA
OFF
ON OFF
4-20mA
OFF
ON OFF
Shunt K2
Shunt K3
A
B
ON OFF
OFF
OFF
ON
OFF
OFF
ON
ON
ON OFF
OFF
ON
OFF
ON
ON
ON OFF
OFF
ON
OFF
ON
ON
27

Publicidad

loading

Este manual también es adecuado para:

Er plus serieEr10 plusEr20 plusEr35 plusEr60 plusEr100 plus