Parameter
11 InFL
T Mand risc= T Mand Curva + ( CLI * InFL * ΔT Amb)
T Mand Curva = Delivery temperature calculated using the thermoregu -
lation curve set under parameter CLI
CLI = thermoregulation curve
InFL = room influence
ΔT Amb = (room temperature set) – (current room temperature)
9
Setting the parameter InFL=0, with the external probe disconnected
from the boiler and the web external probe not enabled on the
app, the heating delivery temperature (for the area controlled by
Hi, Comfort T100) is the same as the temperature set under param -
eter LLCH.
9
By setting parameter InFL >0, with the external sensor not connected to the
boiler and the web external sensor not enabled on the app, the heating de-
livery temperature (for the zone controlled by Hi, Comfort T100) is as follows:
Heating del. T = LLCH + ( InFL * ΔT Amb )
13 CALI
Influence of room probe on calculation
of heating delivery setpoint tempera -
ture (available with OTBus connection
between the WiFi Box and the boiler
or the RF receiver and the boiler or the
ESC
Hi, Comfort T100 and the boiler, if pro -
MODE
vided for by the OTBus protocol).
Default set to 10.
The value can be set from 0°C to 20°C.
Correction of the temperature detected by
the Hi, Comfort T100 room probe.
The value can be set with a hysteresis of
+-7°C.
ESC
MODE
110