Descargar Imprimir esta página

Riello Hi, Comfort 100 Manual Instalador Y Usuario página 112

Ocultar thumbs Ver también para Hi, Comfort 100:

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 188
Parameter
19 HOn
ESC
MODE
19 HOFF
ESC
MODE
21 ALL
ESC
MODE
22 tSP
ESC
MODE
Description
Setting the ON hysteresis for heating or
cooling requests.
The value can be set from 0°C to 2°C; the
default setting is 0.4°C.
The Hi, Comfort T100 processes an ON
request below the target room tem -
perature set (desired room setpoint –
H On) if the heating mode is active, or
above the target room temperature
set (desired room setpoint + H On) if
the cooling mode is active.
Setting the OFF hysteresis for heating or
cooling requests.
The value can be set from 0°C to 2°C; the
default setting is 0.1°C.
The Hi, Comfort T100 processes an OFF
request above the target room tem -
perature set (desired room setpoint +
H OFF) if the heating mode is active, or
below the target room temperature set
(desired room setpoint – H OFF) if the
cooling mode is active.
Alarm history display (available with OTBus
connection between the WiFi Box and the
boiler or the RF receiver and the boiler or
the Hi, Comfort T100 and the boiler, if pro -
vided for by the OTBus protocol). The last 9
alarms generated by the boiler and saved
by the Hi, Comfort T100 are shown.
Setting
boiler
ble with OTBus connection between
the WiFi Box and the boiler or the
RF receiver and the boiler or the
Hi, Comfort T100 and the boiler, if pro -
vided for by the OTBus protocol). This
parameter is set by the Authorised Ser -
vice Centre.
112
parameters
(availa -

Publicidad

loading