Boiler
characteristics
Boiler with variable
delivery temper-
ature (controlled
by communication
bus)
Definition of classes
Class I – On/off room thermostat: a room thermostat that controls the on/off op-
eration of a heater. Performance parameters, including switching differential and
room temperature control accuracy are determined by the thermostat's mechanical
construction.
Class V – Modulating room thermostat, for use with modulating heaters: an elec-
tronic room thermostat that varies the flow temperature of the water leaving the
heater dependent upon measured room temperature deviation from room thermo-
stat set point. Control is achieved by modulating the output of the heater.
Class VI – Weather compensator and room sensor, for use with modulating heaters:
a heater flow temperature control that varies the flow temperature of water leaving
the heater dependent upon prevailing outside temperature and selected weather
compensation curve. A room temperature sensor monitors room temperature and
adjusts the compensation curve parallel displacement to improve room comfort.
Control is achieved by modulating the output of the heater.
Class VIII – Multi-sensor room temperature control, for use with modulating heaters:
an electronic control, equipped with 3 or more room sensors, that varies the flow
temperature of the water leaving the heater dependent upon the aggregated meas-
ured room temperature deviation from room sensor set points. Control is achieved
by modulating the output of the heater.
Hi, Comfort T100 configuration
Connection via communication bus to
the Hi, Comfort T100. Delivery tempera-
ture to the boiler calculated on the basis
of at least 3 distinct room temperatures.
At least 3 Hi, Comfort T100s (sensors)
connected to at least 3 zone valves (ac-
tuators) are required.
71
Class and
contribu-
tion
VIII = 5%