5. Instruction of indicator use
Contact type phase sequence test
1. Connect one end of test lead to indicator (connect L1, L2 and
L3 test lead to the corresponding input jack ) and another end
to alligator clip.
2. When three-phase line is tested, it will clamp the end of test
line with alligator clip to three phase lines in three-phase system
(e.g. U, V and W terminal in three-phase motor).
3. Press "TEST" button. The power light turns green, indicating
the indicator is ready for test. "Clockwise rotation (R)" or
"Counter-clockwise rotation (L)" indicator light is on, indicating
L1-L2-L3 of three-phase system connected to the indicator
is "positive phase" or "negative phase".
Caution
The rotation indicator light will be still on if non-energized
conductor is connected and L1, L2 or L3 test lead is not
connected. Please refer to the detailed information below, the
description of status combination of indicator:
22
Specifications