WARNING: the installation of the device must be exclusively done by
qualified personnel, following the regulations in force and the
guidelines for KNX/EIB installations.
Warnings for KNX/EIB installations
1. The length of the bus line between the 8 channel Easy RF Receiver and the power
supply unit must not exceed 350 metres.
2. The length of the bus line between the 8 channel Easy RF Receiver and the most
distant KNX/EIB device must not exceed 700 metres.
3. If possible do not create ring circuits so as to prevent undesirable signals and
overloads.
4. Keep a distance of at least 4 mm between the individually insulated cables of the bus
line and those of the electric line (figure C).
5. Do not damage the electrical continuity conductor of the shielding (figure D).
WARNING: the unused bus signal cables and the electrical continuity
conductor must never touch elements under power or the earth
conductor!
Good wireless connection recommendations
• Install the receiver in a "central" position in relation to the various RF devices it must
receive commands from.
• Install the receiver as far as possible from all sources of electromagnetic disturbances,
such as electrical motors, electricity meters, electrical appliances.
• Do not install the receiver near or behind metal surfaces.
• Do not install the receiver inside metal electrical panels or junction boxes mounted
inside reinforced concrete walls.