Settings and use of the transmitter
Configuration
It is possible to set the measuring ranges and the unit of the instrument either
by switch and/or via software.
To configure the transmitter, it must not be energized. Then, you
can make the settings required, with the DIP switches (as shown
on the drawing below).When the transmitter is configured, you can
power it up.
Please follow carefully the combinations beside with the DIP switch.
If the combination is wrongly done, the following message will
appear on the display of the transmitter "CONF ERROR". In that
case, you will have to unplug the transmitter, place the DIP switches
correctly, and then power the transmitter up.
Units setting – active switch
To set a unit of measurement, put the on-off
switch 4 of the units as shown below.
Configurations
°C
1
2
Combinations
3
4
Configuration via LCC-S software (option)
It is possible to configure intermediate ranges, an offset...
Example: for a 0-100 °C transmitter, minimum delta is 20 °C.
The instrument can be configured from 0 to +20 °C or from
-10 to +10 °C. In order to compensate a possible drift of the
sensor, it is possible to add an offset to the displayed value
by the TH 110 transmitter: it shows 48% RH, a standard
instrument shows 45% RH. It is then possible, via the
software, to integrate an offset of -3 to the displayed value by
the TH 110 instrument.
The configuration of the parameters can be done either with the DIP switch or via software (you can not
combine both solutions).
Mounting
To mount the transmitter, mount the ABS plate on the wall
(drilling: Ø 6 mm, screws and pins are supplied).
Insert the transmitter on the fixing plate (see A on the drawing beside).
Rotate the housing in clockwise direction until you hear a "click" which
confirms that the transmitter is correctly installed.
Maintenance: please avoid any aggressive
solvent. Please protect the transmitter
and its probes from any cleaning product
containing formalin, that may be used for
cleaning rooms or ducts.
Outputs setting – active switch
To set an output, put the on-off switches 1, 2 and 3 of the
measuring ranges as shown below.
From 0
°F
to +50 °C
1
1
1
2
2
2
3
3
3
4
4
4
PC configuration
Connect the cable
of the LCC-S to the
connection of the
transmitter.
Precautions for use: please always use the device
in accordance with its intended use and within
parameters described in the technical features in order
not to compromise the protection ensured by the
device.
Active switch
1
2
3
4
Off
On
From -20
From -50
to +80 °C
to +50 °C
1
1
2
2
3
3
4
4
1
Please refer to the
user manual of the
2
LCC-S software
3
to make the
4
configuration.