Descargar Imprimir esta página

English; Battery Temperature Compensation Scales - gs yuasa GYT117 Guia Del Usuario

Ocultar thumbs Ver también para GYT117:

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 13

English

Troubleshooting
TOO LO: The battery's Voltage is below the specified operating
range (< 6.00V for a 6V battery or <12.00V for a 12V battery).
Note: If the battery is below 5.5V, the tester will not operate.
TOO HI: The battery's Voltage is above the specified operating
range (> 6.90V for a 6V battery or >13.80 V for a 12V battery).
999 (or 9999 when ENTER is pressed): The battery has exceeded
the range specified. Refer to 'Specifications' for the tester's
operating range.
Excessive electromagnetic interference may cause the tester to
reset. If the tester resets during testing, simply disconnect it from
the battery, reconnect and start the test process again.
Establishing a conductance reference value
Battery performance is temperature dependent. Allow the
batteries to reach room temperature before testing - ideally
around 25°C (77°F). Refer to the following battery temperature
compensation scales below for the compensation factor.
As conductance is a relative measure, you must first establish a
reference value by testing a sample number of new batteries.
To establish a reference value, record the average of at least ten
fully charged batteries of the same or similar models, preferably
within 90 days of their installation. GS Yuasa recommends that the
batteries should all test within 20% of each other (+/–10% of the
average). (Consult your battery supplier for conductance values).
If new batteries are not available, record the average of installed
batteries of the same or similar models regardless of age. If the
installed batteries test within 10% of each other, the highest value
can be used as a temporary reference until new batteries are
available for testing.
6
English
Example: Within 90 days of installation, measure a sample of
20 new batteries (12V, 17Ah) that average 300S each when fully
charged. Conductance will decline as a battery ages. The amount
of acceptable loss will depend on the type of application for which
the battery is used. As a general rule:
<30% loss = Strong battery - no significant capacity loss (300 x 0.70
or more ≥210S)
30 to 40% loss = Marginal battery - nearing the end of its
serviceable life (180 to 210S)
>40% loss = Degraded battery - may not meet the required load
(300 x 0.60 or less ≤180S)
Consult your battery supplier to ensure that the rated battery
capacity is sufficient for the applicable equipment runtime while
allowing for the appropriate aging factor of the batteries.

Battery temperature compensation scales

Battery temperature
35°C (95°F) or warmer
30°C (86°F)
25°C (77°F)
20°C (68°F)
15°C (59°F)
10°C (50°F)
5°C (41°F)
0°C (32°F) or colder
Examples:
Using a reference value of 300, the GS Yuasa GYT117 reports 63%,
190S. If the battery temperature is 35°C (0.63 x 0.93 = 0.59 or 59%),
the battery should be replaced.
Again using a reference value of 300, the GS Yuasa GYT117 reports
63%, 190S. If the battery temperature is 0°C (0.63 x 1.175 = 0.74 or
74%), the battery is good.
For a full list of Siemens values for Yuasa battery types visit
www.yuasa.com/GYT117
7
Multiply GS Yuasa
%Ref. value by
0.930
0.965
1.000
1.035
1.070
1.105
1.140
1.175

Publicidad

loading