If there are any problems with the functioning of the chimney, these must be solved before installing the
stove.
When connecting the stove to the smoke drain and flue tubes, carefully check if all connections are sealed to
make sure that no gasses escape to the room.
4.2 Position of the stove/distance requirements
Distance requirements will only apply if the stove is to be placed close to flammable materials. See the table
and illustration below:
Distance to flammable material (see also illustration below)
Behind the stove
100 mm
To secure access to inspection openings and enough air for the combustion, there needs to be a distance of
at least 10 cm to the wall behind and 40 cm to the side. You must be prepared to dismount the flue pipe and
turn the stove during the yearly inspection and by maintenance.
If stove is to be placed close to flammable material such as a wooden floor or carpet it must be placed on a
non-flammable base. The floor plate should extend for at least 30 cm in front of the stove and 15 cm on each
side – measured from the combustion chamber opening.
The stove must be installed on a floor with the adequate load-bearing capacity. If
the existing construction does not meet this requirement, appropriate adaptation
measures must be taken (e.g. a load-distributing plate).
To the sides
400 mm
To furniture
700 mm
To the top
400 mm
45