ENGLISH
INSTRUCTION FOR USE: 4-/6-PORT LINE REGULATOR
EN
1. GENERAL
1.1. INFORMATION ABOUT THIS INSTRUCTIONS MANUAL
This instruction is only intended for use with line regulator product type:
•
R200
•
R300
•
R500
Line regulators of this type are suitable to reduce a high supply pressure through diff erent pressure stages.
These regulators were assembled into piping system permanently.
These instructions enable you to operate the system safely and effi ciently. These instructions form an integral
part of the system and must always be kept with the system and within easy reach of staff at all times.
Prior to commencing any work, the staff must read these instructions carefully and understand the contents.
Observance of all the safety information and instructions for operation that are contained in these instructions
is essential to ensure work safety.
Local accident prevention regulations and general safety regulations governing the use of the system must
also be observed.
Illustrations in these instructions serve to ensure a basic understanding of the system and may diff er from
the actual version.
1.2. INFORMATION ABOUT THIS LINE REGULATOR
Line Regulators of this type are only suitable for gases defi ned as standard gas. The maximum working pres-
sure for line regulator is 300 bar.
Product Line
High Pressure Regulator
with
FKM
High Pressure Regulator with
EPDM
Relief Valve Seat
This table is not exhaustive. For questions and ambiguities please contact manufacturer.
Relief Valve Seat
(Purity 6.0 | brass chrome plated)
•
Suitable Gases
(including their mixtures)
•
High Purity
•
Inert
•
Flammable
•
Oxidizing
•
Use for O2
•
Not Suitable Gases
(including their mixtures)
•
Corrosive
•
Toxic
•
Not for CO2, N2O
•
Suitable Gases
(including their mixtures)
•
High Purity
�
Inert
•
Flammable
•
Oxidizing
•
Use for CO2, N2O
•
Not Suitable Gases
(including their mixtures)
•
Corrosive
•
Toxic
•
Not for O2
(share greater than 21%)
•
Hydrocarbons
4/298
(Purity 6.0 | stainless steel)
•
Suitable Gases
(including their mixtures)
•
High Purity
�
Inert
•
Flammable
•
Oxidizing (up to 200 bar)
•
Corrosive (in doubt ask)
•
Toxic (in doubt ask)
•
Not Suitable Gases
(including their mixtures)
•
Not for O2 above 200 bar
and share
greater than 21%
•
Not for CO2, N2O
•
Not for NH3, SO2, H2S
•
Suitable Gases
(including their mixtures)
•
High Purity
•
Inert
•
Flammable
•
Oxidizing
•
Corrosive (in doubt ask)
•
Toxic (in doubt ask)
•
Use for CO2, N2O
•
Use for NH3, SO2, H2S
•
Not Suitable Gases
(including their mixtures)
•
Not for O2
(share greater than 21%)
•
Hydrocarbons