Technical data

Voltage range
LED nominal voltage
LED tolerances
ELV indication LED
Response time
Peak current
Measurement duty
Internal battery consumption
Single-pole phase test voltage range
Phase rotation test
Continuity test
Battery
Temperature
Humidity
Altitude
Overvoltage
Standard
Pollution degree
Protection

Cleaning and storage

Tester does not need any special maintenance if used according to user manual.
Remove tester from all test points before cleaning.
Use a lightly damp cloth with neutral detergent for cleaning the instrument. Do
not use abrasives or solvents. After cleaning, do not use the device until it is
completely dry.
Do not expose the instrument to direct sun light, high temperature and humidity
or dewfall.
Remove batteries when the instrument will not be in use for a long period to
prevent danger or damage due to possible battery leakage.
12�1,000 V AC (16 2/3�950 Hz),
12�1,500 V DC)
12/24/50/120/230/400/690/1,000 V,
AC (16 2/3�950 Hz), DC(±)
according to EN 61243-3
> 50 V AC, > 120 V DC
< 0,5 s at 100 % of each nominal voltage
Is < 3.5 mA (at 1,000 V)
30 s ON (operation time), 240 s OFF
(recovery time)
approx. 80 mA
100�1,000 V AC (40...70 Hz)
170�1,000 V phase-to-phase,
AC 50/60 Hz
detection range 0�500 kΩ + 50 %
3 V (IEC LR03 1.5 V x 2)
-15�50 °C operation; -20�60 °C
storage, No condensation
max. 85 % RH
up to 2,000 m
CAT. III 1,000 V / CAT. IV 600 V
EN 61243-3:2014
2
IP64
EN
17