5.5.2
Power supply control unit 24 V
The product can be directly connected to the DC supply (for example, of
a control cabinet or a PLC).
1. Open the control unit.
2. Route the mains cable through the left cable gland into the control unit.
3. Connect the wires to the terminals L and N. Any polarity is permissible.
- The power supply unit features protection against reverse polarity.
5.5.3
Connecting the photoelectric probes
Use a cable with 3 x 1 mm² to extend the probe cable. Use shielded
cables for lengths of more than 15 m. The maximum length of the probe
cables is 50 m. Use underground cables such as NYY 3 x 1.5 mm² for
underground cable installation.
Verify that the probe cable is sufficiently protected from damage (for
example, by installing it in a metal pipe).
Verify that the probe cable is not routed immediately next to or together
with cables carrying mains voltage.
1. Route the probe cable through the cable gland at the right.
2. Connect the wires of the probe cable as follows:
- Green to terminal OUT
- Brown to terminal GND
- White to terminal IN
Mounting
23
AFA 11
EN