Keep this manual easily accessible for all
users.

Important safety instructions:

•  Only use for dry and clean gases For use
with aggressive gases please contact
ITRON for special versions Never use with
oxygen: Danger of explosion!
•  Please respect all national standards and
codes of practices for installation, opera-
tion, testing and service of gas products
and of gas pressure regulating stations
•  Before mounting please check the product
for possible damage due to transport The
sealing surfaces must be clean
•  Arrange enough room for the serving of
the product
•  To protect the product from dirt a sieve or
a filter is recommended
•  The product must be installed tension free
in the piping
•  After installation please check the tight-
ness of the thread connection
•  The technical data given on the name plate
must be respected If necessary safety de-
vices must be installed
•  Repairs and maintenance must be done by
trained or qualified personal Afterwards a
tightness test with 1 1 x PS must be per-
formed When changing pressure contain-
ing parts their compliance with the PED
must be assured
•  If used with wet gas, internal and external
effect of corrosion has to be checked reg-
ularly and in case of severe corrosion, the
product has to be replaced
•  Please don't use solvent or alcohol contain-
ing products to clean the product
•  Before removing the product please de-
pressurize completely Some gas may still
be inside the product and the pipe, there-
fore sufficient ventilation is required
Instructions for use in potentially
explosive atmospheres (ATEX):
•  If film of rust is possible (flying rust in the
immediate product surroundings), all out-
er aluminum parts shall be protected ap-
propriately (e g by varnish)
•  The product must be electrically connect-
ed to adequately earthed installation
•  For installation, removing or repair of the
product on site, only tools allowed for the
corresponding explosion area can be used
•  The product shall not be exposed to flames,
ionized radiation or ultrasound