The control unit is supplied by the manufacturer with the DS1
safety device operating as follows: action is not taken into
account during the opening stage but causes inverted motor
action during the closing stage. If you wish to make it possible
to intervene in the opening or closing process, causing the
motor to stop immediately, proceed as follows: use the SEL
button to reach the stage where the SEL DS1 LED is flashing
and press the SET button: the SEL DS1 LED lights up in a
constant manner and programming is completed. Repeat the
operation to restore the previous configuration.
7) SEL DS2:
(Selection of Safety Device 2)
The control unit is supplied by the manufacturer with the DS2
safety device operating as follows: action is not taken into
account during the opening stage but causes inverted motor
action during the closing stage. If you wish to make it possible
to intervene in the opening or closing process, causing the
motor to stop immediately and a brief inversion in the motor
direction, proceed as follows: use the SEL button to reach a
stage where the SEL DS2 LED is flashing and press the SET
button: the SEL DS2 LED lights up in a constant manner and
programming is completed. Repeat the operation to restore the
previous configuration.
8) SEL DS3:
(Selection of Safety Device 3)
The control unit is supplied by the manufacturer with the DS3
safety device operating as follows: action is not taken into
account during the opening stage but causes inverted motor
action during the closing stage. If you wish to make it possible
to intervene in the opening or closing process, causing the
motor to stop immediately, proceed as follows: use the SEL
button to reach a stage where the SEL DS3 LED is flashing and
press the SET button: the SEL DS3 LED lights up in a constant
manner and programming is completed. Repeat the operation to
restore the previous configuration.
EXTENDED MENU
The control unit is supplied by the manufacturer with the
possibility of selecting only the functions listed in the main
menu.
To enable the functions of the extended menu proceed as
follows: press and hold the SET button for 5 seconds; the DS2
and DS3 LEDs will start flashing alternately. the user then has
30 seconds in which to select the functions of the extended
menu using the SEL and SET buttons, after 30 seconds the
control unit returns to the main menu.
---------------------- EXTENDED MENU -----------------
Reference LED
LED Off
A) CODE
remote PGM = OFF
ON
B) INB.CMD.AP.
Test DS1 = OFF
C) LAMP/CORT
Test DS2 = OFF
D) T. MOT.
Test DS3 = OFF
E) T. PAUSA
DS2 intervention = Close
Open
F) SEL DS1
DS3 intervention = Close
Open
G) SEL DS2
G) SEL DS3
A) CODE
(Remote programming of radio control):
The control unit allows the transmission code to be programmed
by remote, without using the SEL button.
To programme the transmission code remotely proceed as
follows: send the radio control code continuously for more than
10 seconds; the control unit will enter the programming mode as
described above for the CODE LED in the main menu.
The control unit is supplied by the manufacturer with remote
programming of the transmission code not enabled; to enable
the function proceed as follows: check that the extended menu
is enabled (DS2 and DS3 LEDs flash alternatively), using the
LED On
remote PGM =
Test DS1 = ON
Test DS2 = ON
Test DS3 = ON
DS2 intervention =
DS3 intervention =
Flashing beacon ON/OFF
Flashing beacon ON/OFF
"SEL" button navigate to CODE LED when flashing and press
the "SET" button: the CODE LED lights up and programming is
completed. Repeat the operation to restore the previous
configuration.
B) INB.CMD.AP. (Test DS1 safety device):
The control unit allows the photoelectric cells to be powered and
connected according to regulation EN 12453 (please read
"Notes for the Installer" carefully).
The control unit is supplied by the manufacturer with the DS1
safety device disabled. To activate the test in accordance with
regulation EN 954-1 cat. 2 relating to protection against failures,
proceed as follows: check that the extended menu is enabled
(DS2 and DS3 LEDs flash alternatively), using the "SEL" button
navigate to INB.CMD.AP LED when flashing and press the
"SET" button: the INB.CMD.AP LED lights up and programming
is completed. In this mode the control unit must use
photoelectric cells connected to the DS1 input; otherwise it is
not enabled for operation.
Repeat the operation to restore the previous configuration.
C) LAMP/CORT (Test DS2 safety device):
The control unit can be connected to a balanced pneumatic
tube (8.2K ohm +/- 10%) in accordance with EN regulation
12453 and EN 60335-2-97 (please read "Notes for the Installer"
carefully).
The control unit is supplied by the manufacturer with the DS2
safety device disabled. To activate the test in accordance with
regulation EN 954-1 cat. 2 relating to protection against failures,
proceed as follows: check that the extended menu is enabled
(DS2 and DS3 LEDs flash alternatively), using the "SEL" button
navigate to LAMP/CORT LED when flashing and press the
"SET" button: the LAMP/CORT LED lights up and programming
is completed.
In this mode the control unit must use the security device
connected to the DS2 input; otherwise it is not enabled for
operation.
Repeat the operation to restore the previous configuration.
C) T.MOT (Test DS3 safety device):
The control unit can be connected to a balanced pneumatic
tube (8.2K ohm +/- 10%) in accordance with EN regulation
12453 and EN 60335-2-97 (please read "Notes for the Installer"
carefully).
The control unit is supplied by the manufacturer with the DS3
safety device disabled. To activate the test in accordance with
regulation EN 954-1 cat. 2 relating to protection against failures,
proceed as follows: check that the extended menu is enabled
(DS2 and DS3 LEDs flash alternatively), using the "SEL" button
navigate to T. MOT LED when flashing and press the "SET"
button: at that moment the T. MOT LED lights up in a constant
manner and programming is completed.
In this mode the control unit must use the security device
connected to the DS3 input; otherwise it is not enabled for
operation.
Repeat the operation to restore the previous configuration.
E) T. PAUSA (DS2 intervention mode):
The control unit is supplied by the manufacturer with the DS2
safety device intervention mode operating as follows: Input
closed = safety device intervention; input = 8K2 Ω, normal
safety device operation; input open = error status. If you wish to
modify the safety device intervention mode, proceed as follows:
check that the extended menu is enabled (DS2 and DS3 LEDs
flash alternatively), using the "SEL" button navigate to PAUSA
LED when flashing and press the "SET" button: at that moment
the PAUSA LED lights up in a constant manner and
programming is completed. In this mode the control unit will
modify the safety device intervention as follows: Input closed =
error status; input = 8K2 Ω, normal safety device operation;
input open = safety device intervention.
F) SEL DS1 (DS3 intervention operating mode):