Electrical & installation requirements
IMPORTANT
Observe all governing codes and ordinances.
It is the customer's responsibility:
• To contact a qualified electrical installer.
• To assure that the electrical installation is adequate and in
conformance with National Electrical Code, ANSI/NFPA 70
— latest edition*, or CSA Standards C22.1-94, Canadian
Electrical Code, Part 1 and C22.2 No.0-M91-latest edition**
and all local codes and ordinances.
• If codes permit and a separate ground wire is used, it is
recommended that a qualified electrician determine that
the ground path is adequate.
• Do not ground to a gas pipe.
• Check with a qualified electrician if you are not sure range
hood is properly grounded.
• Do not have a fuse in the neutral or ground circuit.
IMPORTANT
• Save Installation Instructions for electrical inspector's use.
• The range hood must be connected with copper wire only.
• The range hood should be connected directly to the fused
disconnect (Or circuit breaker) box through metal
electrical conduit.
• Wire sizes must conform to the requirements of the
National Electrical Code ANSI/NFPA 70 — latest edition*,
or CSA Standards C22.1-94, Canadian Electrical Code Part
1 and C22.2 No. 0-M91 - latest edition** and all local codes
and ordinances.
Dimensions and clearances
F
G
A
4
E
C
D
H
I
B
• A U.L.- or C.S.A.-listed conduit connector must be
provided at each end of the power supply conduit (at the
range hood and at the junction box).
Copies of the standards listed may be obtained from:
* National Fire Protection Association Batterymarch Park Quincy,
Massachusetts 02269
** CSA International 8501 East Pleasant Valley Road Cleveland,
Ohio 44131-5575
BEFORE INSTALLING THE HOOD
1 For the most efficient air flow exhaust, use a straight run
or as few elbows as possible.
CAUTION: Vent unit to outside of building, only.
2 At least two people are necessary for installation.
3 Fittings material is provided to secure the hood to most types of
walls/ceilings, consult a Qualified Installer,check if they perfectly fit
with your cabinet/wall.
4 Do not use flex ducting.
5 COLD WEATHER installations should have an additional
backdraft damper installed to minimize backward cold air flow and
a nonmetallic thermal break to minimize conduction of outside
temperatures as part of the ductwork. The damper should be on
the cold air side of the thermal break.The break should be as close
as possible to where theducting enters the heated portion of the
house.
6 Make up air: Local building codes may require the use of
Make-Up Air Systems when using Ducted Ventilation Systems
greater than specified CFM of air movement.The specified CFM
varies from locale to locale. Consult your HVAC professional for
specific requirements in your area.
PCHLC630SS
A
30" (76 cm)
B
C*
D**
E
F
G
H
I
*
Ductless (Recirculating) version
** Ducted version
Models
PCHLC636SS
36" (91.2 cm)
⁄
19
" (50.5 cm)
7
8
⁄
Max: 42
" (107.3 cm)
1
4
⁄
Min: 28
" (71.8 cm)
17
64
⁄
Max: 38
" (98.3 cm)
45
64
⁄
Min: 24
" (62.5 cm)
39
64
6" (15.2 cm)
⁄
10
" (26.8 cm)
35
64
⁄
13
" (33.1 cm)
1
32
⁄
23
" (60.8 cm)
15
16
⁄
4
" (12.6 cm)
61
64