1(PLC: 40002)
Setting the mode
Setting water water
temperature T1S
2(PLC: 40003)
3(PLC: 40004)
Setting air temperature Ts
4(PLC: 40005)
T5s
5(PLC: 40006)
Function Setting
6 (PLC: 40007)
Curve selection
7(PLC: 40008)
Forced water heating
8 (PLC: 40009)
Forced TBH
9(PLC: 40010)
Forced IBH1
10(PLC: 40011)
t_SG_MAX
11(PLC: 40012)
T1S
12(PLC: 40013)
T1S
13(PLC: 40014)
t_ANTILOCK
Leaving water temperature T1s setting range instruction:
In cooling mode, T1S low temp setting range is 5~25°C;T1S high temp setting range is 18~25°C.
In heating mode, T1S low temp setting range is 22~55°C;T1S high temp setting range is 35~70°C.
1: Auto; 2: Cool; 3: Heat;
Others: Invalid
Bit8-Bit15
Water temperature T1s is corresponding to the floor heating.(zone 2)
Bit0-Bit7
Water temperature T1s is corresponding to the floor heating.(zone 1)
The room temperature range is between 17°C and 30°C, and is valid when there is Ta.
Portocol value=actual value*2
The water tank temperature range is between 20°C and 65°C.
BIT15
Reserved
BIT14
Reserved
BIT13
1: climate curve setting is valid; 0: climate curve setting is invalid. (zone2)
BIT12
1: climate curve setting is valid; 0: climate curve setting is invalid. (zone1)
BIT11
DHW pump's running constant-temperature water recycling
BIT10
ECO mode
BIT9
Reserved
BIT8
Holiday home (the status can only be read, not changed)
BIT7
0: Silent mode level1; 1: Silent mode level2
BIT6
Silent mode
BIT5
Holiday away (the status can only be read, but cannot be changed)
BIT4
Disinfect
BIT3
Reserved
BIT2
Reserved
BIT1
Reserved
BIT0
Reserved
Bit8-Bit15
Climate Curve 1-9(zone 2)
Bit0-Bit7
Climate Curve 1-9(zone 1)
0: Invalid
TBH is the electric water tank heater.
1: Forced
IBH1 and 2 are the hydraulic module's rear electric heater.
on
IBH1 and 2 can be activated together.
2: Forced
TBH cannot be activated together with IBH1 and IBH2.
off
Water temperature T1S is corresponding to the floor heating.(zone 1)
Water temperature T1S is corresponding to the floor heating.(zone 2)
Default setting: 5, range: 0~60 S(Available in Sphera A)
50
0-24 Hours
V.1