Descargar Imprimir esta página

Technical Data - pizzato CS MP207 Serie Manual

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 16
a) In nuclear power stations, trains, airplanes, cars, incinerators, medical devices or
any application where the safety of two or more persons depend on the correct opera-
tion of the device.
b) Applications not contemplated in this instruction manual.
8 MARKINGS
The outside of the device is provided with external marking positioned in a visible
place. Marking includes:
- Producer trademark
- Product code
- Batch number and date of manufacture. Example: CS1-123456 (A20). The last part
of the production batch refers to the month of manufacture (A = January, B = February,
etc.) as well as the year of manufacture (20 = 2020, 21 = 2021, etc.).

9 TECHNICAL DATA

9.1 Housing
Material: Polyamide PA 66, self-extinguishing V0 acc. to UL 94
Protection degree:
Cable cross section:
Terminal tightening torque:
9.2 General data
SIL:
Performance Level (PL):
Safety category:
MTTF
:
D
DC:
PFh
:
D
Mission time:
System response time:
Ambient temperature:
Storage temperature:
Pollution degree:
Overvoltage category:
Air and surface distances:
9.3 Power supply (A1-A2)
Rated supply voltage U
:
n
Supply voltage tolerance:
Max. residual ripple:
Rated consumption (w/o load):
Internal general protection:
PTC response time:
Internal protection against short circuits on outputs (Tx, Ox): electronic
Maximum current output of the module as the total current of the Ox and Tx outputs:
Self-test duration on startup:
9.4 Input circuits (Ix)
Number of inputs:
Voltage and current in the input circuits: 24 V, 5 mA
Input signals:
Galvanic separation:
Minimum duration of input signal:
Input signal filtering:
Maximum input resistance:
Maximum input capacitance:
9.5 Analogue input circuits (Cx)
Number of inputs:
Rated supply voltage:
Analogue input type:
Measurement range:
Accuracy over entire measurement range: 1 % ± 1 digit
Resolution:
Input resistance:
Maximum applicable current:
Managed sensors:
Galvanic separation:
IP40 (housing), IP20 (terminal strip)
0.2 ... 2.5 mm
(24 ... 12 AwG)
2
0.5 ... 0.6 Nm
Up to SIL 3 acc. to EN 62061
Up to PL e acc. to EN ISO 13849-1
Up to cat. 4 acc. to EN ISO 13849-1
431 years
high
7.08 E-09
20 years
< 30 ms
0°C ... +55°C
-20°C ... +70°C
external 3, internal 2
II
acc. to EN 60947-1
24 Vdc
±15% of U
n
10%
< 3 w
PTC, Ih=1.5 A
response time > 100 ms, release time > 3 s
0.5 A
< 2 s
4
0-8 V (Off), 12-24 V (On)
no
10 ms
yes, maximum interference period 0.4 ms
100 Ω
470 nF to ground
470 nF between two conductors
2
24 Vdc ± 15 %
4-20 mA current loop
0 ... 25 mA
0.01 mA
100 Ohm
30 mA
"source" type with 2/3 wires
Yes
Insulation voltage (Ui):
NB: Voltage and current values indicated refer to the power supply terminals (Ax, see each module
individually) of the board where the Cx type terminals are present
9.6 Circuits with Test signals (Tx)
Number of test signals:
Signal type:
Max. current per test signal:
Max. total current:
Protected against short circuit:
Galvanic separation:
9.7 Semiconductor signalling output circuits (Ox)
Number of outputs:
Output type:
Maximum current per output:
Max. total current:
Impulse withstand voltage (U
imp
Rated insulation voltage (U
):
i
Protected against short circuit:
Galvanic separation:
9.8 Semiconductor safety output circuits (OSx)
Number of outputs:
Rated voltage 24V-0V:
Output type:
Maximum current per output:
Max. total output current:
Minimum current:
Maximum capacitive load to ground per output: 400 nF
Maximum inductive load per output:
Protection fuse:
Galvanic separation:
Impulse withstand voltage (U
imp
Rated insulation voltage (U
):
i
Short circuit detection between outputs: yes
Duration of the deactivation impulses at the safety outputs: < 300 µs
9.9 Compliance with standards
EN 60204-1, EN ISO 13855, EN ISO 14118, EN ISO 12100, EN ISO 13850, EN 60529,
EN 61000-6-2, EN 61000-6-3, EN 61326-1, EN 61326-3-1, EN 60664-1, EN 60947-1,
EN 60947-5-1, EN IEC 63000, EN ISO 13849-1, EN ISO 13849-2, EN 62061,
EN 62326-1, EN 61131-6, UL 508, CSA C22.2 n° 14, GB/T14048.5-2017
9.10 Compliance with directives
Machinery Directive 2006/42/EC, EMC Directive 2014/30/EU, RohS Directive
2011/65/EU.
10 SPECIAL VERSIONS ON REQUEST
Special versions of the device are available on request.
These special versions may differ substantially from the indications in these operating
instructions.
The installer must ensure that he has received written information regarding the use
of the special version requested (see paragraph SUPPORT).
11 DISPOSAL
At the end of service life product must be disposed of properly, according to the
rules in force in the country in which the disposal takes place.
12 SUPPORT
The device can be used for safeguarding people's physical safety, therefore in case of
any doubt concerning installation or operation methods, always contact our technical
support service:
Pizzato Elettrica Srl
Via Torino, 1 - 36063 Marostica (VI) - ITALY
Telephone +39.0424.470.930
E-mail tech@pizzato.com
www.pizzato.com
Our support service provides assistance in Italian and English.
6/23
500 V
4
pulsed 100 hz 24V/0V, duty cycle 50%
0.2 A
See Power supply (A1-A2)
yes
no
4
PNP
0.5 A
See Power supply (A1-A2)
):
0.8 kV
32 V
yes
no
4
24 Vdc
PNP
0.5 A
2 A
10 mA
500 mh
2 A type gG
yes
):
0.8 kV
32 V