ADJUSTING THE TEMPERATURE

Temperature limiter:
• All mixers are fitted with the maximum temperature limiter pre-set at the factory to reduce the risk
of scalding.
• Where group thermostatic mixing valves are installed, the temperature limiter MUST BE REMOVED
from all point-of-use mixers.
• Recommended maximum temperature settings for UK healthcare applications are: bidets 38°C,
washbasins and showers 41°C. For all other countries please refer to the relevant hot water safety
guidelines.
Adjusting the mixed water temperature limiter:
• To adjust the pre-set maximum temperature, unclip and reposition the index ring located beneath
the control lever.
• The position of the index ring will limit the water temperature at the mixer outlet.
• To access the cartridge (Fig. AF), remove the control lever by removing the cover cap (Fig. AA),
unscrew the grub screw using a 2.5mm Allen key (Fig. AB), and remove the control lever and remove
the cover cap on the mixer body (Fig. AC to AE).
• To change the hot water (HW) setting, unclip the index ring (Fig. AH) and turn clockwise to increase
the hot water temperature, or anti-clockwise to lower it. Replace the index ring and check
the temperature at the mixed water outlet is at the desired maximum temperature.
MAINTENANCE
• Our mixers will withstand thermal and chemical shocks as described by current guidelines.
• Check that the cartridge is operating correctly at least once a year, and more frequently if necessary.
In case of malfunction, replace the cartridge.
• The filters must be checked at least once a year and more often if the water quality necessitates.
• In the event of malfunction, de-scale or replace worn or damaged parts.
• Across all mixers, the torque required to hold the cartridge in the mixer body should be between 8
and 10 Nm to avoid leaks.
MAINTENANCE & CLEANING
• Cleaning chrome, aluminium and stainless steel: do not use abrasive, chlorine
or any other acid-based cleaning products. Clean with mild soapy water using a cloth or a sponge.
• Frost protection: drain the pipes and operate the mixer/tap/valve several times to drain any
remaining water. In the event of prolonged exposure to frost, we recommend taking the mechanisms
apart and storing them indoors.
For the UK market only: Tel. 01491 821 821 - email: technical@delabie.co.uk
For all other markets: Tel. +33 (0)3 22 60 22 74 - email: sav@delabie.fr
After Sales Care Support:
The installation guide is available on: www.delabie.co.uk
The installation guide is available on: www.delabie.com
EN

Publicidad

loading

Este manual también es adecuado para:

Biosafe 2665