 P 04 = water sensor:
- 000: not available
- 001: available
Based on the set value, the sensor alarm and the heating
element functions will be controlled
 P 05 = use logic – Digital input 1 for Cooling/Heating
switching:
- 000: (open/closed) = (Cooling/Heating)
- 001: (open/closed) = (Heating/Cooling)
 P 06 = use logic – Digital input 2 for On/Off switching:
- 000: (open/closed) = (On/Off)
- 001: (open/closed) = (Off/On)
PARAMETER CONFIGURATION PROCEDURE
 S witch the thermostat off
 P ush the keys at the same time
 U se keys
to modify the display value up to the
password value 10, and press
If it is correct, you will have access to the parameters
Value of selected
parameter
Selected
parameter P...
 U se keys
to scroll the various parameters (see
"Parameter list" described above)
 P ress
to confirm the parameter change (the value
will start flashing).
Installation and operation manual
2
level indication:
1= password entry
.
level indication:
001= password
entry
level indication:
003 = password entry
 u se keys
to change the value
 P ress
to save the new value setting or
the modification
 A fter completing the modification of the parameters
concerned press key
NB The parameter configuration phase is of limited duration.
Once a certain time has elapsed (around 2 minutes) the
thermostat will switch back into the Off status and only the
saved changes will be retained.
AVAILABLE CONFIGURATIONS (PARAMETER P00)
The LCD controller can be configured in various ways
according to the type of system. Various configurations can
be obtained through the P00 parameter (see configuration
procedure of controller parameters).
001
 S ystem pipes: 2
 V alve: NO
 H eating element: NO
 F an speed: 3
 S ummer/winter switching logic: LOCAL MANUAL
002
 S ystem pipes: 2
 V alve: NO
 H eating element: NO
 F an speed: 3
 S ummer/winter switching logic: REMOTE MANUAL
003
 S ystem pipes: 2
 V alve: NO
 H eating element: NO
 F an speed: 3
 S ummer/winter switching logic: AUTOMATIC WATER SIDE
004
 S ystem pipes: 2
 V alve: NO
 H eating element: NO
 F an speed: 4
 S ummer/winter switching logic: LOCAL MANUAL
005
 S ystem pipes: 2
 V alve: NO
 H eating element: NO
 F an speed: 4
 S ummer/winter switching logic: REMOTE MANUAL
006
 S ystem pipes: 2
 V alve: NO
 H eating element: NO
 F an speed: 4
 S ummer/winter switching logic: AUTOMATIC WATER SIDE
to cancel
to exit the procedure
FWEC1
Standard electronic controller
FC66002763