ELECTRICAL WIRING
b. Lead the cable through the conduit tube in the wall.
Implanted switch box
(JIS Box) for 2 switches
M4 screws
(field-supplied)
c. Peel the insulation at the end of the cable and clamp the
M3 solderless terminals (field-supplied).
Connect the terminals
3 ELECTRICAL WIRING
Wiring Example (Using a twist pair cable with shield tube)
Max 16 indoor units
Remote
Electrical box
control switch
of indoor unit
Terminal board
A
B
REMOCON
REMOCON
M3.5
A
B
screws
M3
screws
Twist pair cable with shield tube: 1P-0.75mm
!
C A U T I O N
Always make sure to turn off the power of the indoor unit when performing
electrical wiring work. Performing electrical wiring work with the power on
can damage the circuit boards of the indoor unit and the remote control
switch.
Remote control cable <option> Model: PRC-x K
Twist pair cable (1P-0.75mm
Diameter: Ø 7
Color: Ivory
50mm
The number of x indicates the length (m) of the cable (x=2, 3, 5,
8, 10, 15, 20, 30, 50, 75, 100).
The cable of 30m and over is available by ordering.
3
PMML0404A rev.1.1 - 06/2022
Implanted switch box
(JIS Box) for 1 switch
Remote control
switch
Electrical box
(Subsidiary)
of indoor unit
Terminal board
A
B
REMOCON
REMOCON
M3.5
A
B
screws
or more
2
)
2
Solderless Tern (X Type)
1.25-3X
100mm
3 Attach the remote control switch to the holding bracket. Be
careful not to pinch the cable when attaching it.
4 Remove the protection film from the liquid crystal display.
Remove the protection film
?
N O T E
Use a 0.3 to 0.75mm
2
total cable length is 30m. If the total cable length exceeds
30m, use a twist pair cable with shield tube (1P - 0.75mm
In that case, the maximum total cable length is 500m.
If using in combination with the control timer, the allowable total cable
length is up to 100m. The use of a cable other than that specified
above can cause of malfunction due to effects of noise.
Keep a distance more than 30cm between the transmission line
(remote control switch cable and transmission wires) and power
source of the indoor units. If not, the air-conditioner may not operate
properly or malfunction may occur due to effect of power source
noise.
In case of simultaneously controlling multiple indoor units, set the
refrigerant cycle numbers and addresses of the indoor units without
overlapping.
Refer to the Technical Catalog provided with each indoor unit when
performing electrical wiring work between the remote control switch
and indoor units for setting the refrigerant cycle number and the
indoor unit address.
No gap shall exist between the remote control switch cable and hole
of the remote control switch case. If there is a gap, cover the gap
with vinyl tape. If not, malfunction may occur due to entrance of water
droplets or insects.
In case of operating with two remote control switches (Main and
Sub), set the main and sub remote control switches by selecting the
appropriate function with the remote control switches according to
the chapter
"6 Function Selection and
off the power supply of all the indoor unit connected to the remote
control switches.
The control timer cannot be used together with this remote control
switch.
cable for connecting. The maximum
setting". After setting it, turn
).
2