10. Technical data
Operating conditions
Sound pressure level
Relative humidity
System pressure
Inlet pressure
Maximum inlet pressure
Ambient temperature
Liquid temperature
Liquid
Viscosity
Maximum altitude of installation
Electrical data
Supply voltage
Insulation class
Standby power consumption
Inrush current
Minimum switching time power on/off
Miscellaneous data
Motor protection
Enclosure class
Temperature class (TF)
Specific EEI values
To avoid condensation in the stator, the liquid temperature must
always be higher than the ambient temperature.
10.1 Reduced supply voltage
The pump operation is ensured above 160 VAC with reduced
performance.
If the voltage falls below 190 VAC, a low-voltage warning is sent via
the PWM signal.
If the voltage falls below 150 VAC, the pump stops and shows an
alarm.
22
The sound pressure level of the pump is lower than 32 dB(A).
Maximum 95 %, non-condensing environment
PN 10: Maximum 1.0 MPa (10 bar)
Liquid temperature
75 °C
95 °C
1 MPa (10 bar)
0-55 °C
2-95 °C
Maximum water/propylene glycol mixture is 50 %
2
Maximum 10 mm
/s
2000 m above sea level
1 x 230 V - 15 %/+ 10 %, 50/60 Hz, PE
F
< 1 W
< 4 A
No specific requirements
The pump requires no external motor protection.
IPX4D
TF95
ALPHA1 L XX-40: EEI ≤ 0.20
ALPHA1 L XX-60: EEI ≤ 0.20
ALPHA1 L XX-65: EEI ≤ 0.20
ALPHA1 L XX-80: EEI ≤ 0.20
Minimum inlet pressure
0.005 MPa (0.05 bar), 0.5 m head
0.05 MPa (0.5 bar), 5 m head