7.1.1 Setting the start levels with a controller
LC 220
Select a start level, either "LOW" or "HIGH", via the
DIP switches. The stop and alarm levels are set
automatically according to the selected start level.
LOW
Start level
180
[mm]
Stop level
100
[mm]
Alarm level
350
[mm]
See the installation and operating instructions of the
controller for more information about the DIP
switches.
You can change the values corresponding to "LOW"
and "HIGH" via PC Tool, which is available as an
accessory. Product number: 96705378.
LC 221
Go go [Setup], [L_01] and select one of the following
start levels. The stop and alarm levels are set
automatically according to the selected start level.
1
Start level
180
[mm]
Stop level
100
[mm]
Alarm level
350
[mm]
7.1.2 Setting the start levels with float switches
Set the start and stop levels by adjusting the free
cable length (L).
Start
Stop
Fig. 26
Example of start and stop levels for
Unilift CC
HIGH
500
100
600
2
3
4
5
250
350
450
500
100
100
100
100
400
550
600
600
L
We recommend start and stop levels corresponding
to a cable length between the minimum and
maximum values indicated below.
Cable length (L)
Unilift KP
70 mm
(minimum)
Start
Unilift KP
150
290
Unilift KP
250
Unilift KP
300
350
Cable length (L)
Unilift CC
100 mm
(minimum)
Start
Unilift CC 5
350
Unilift CC 7
Unilift CC 9
350
Cable length (L)
Unilift
APB
100 mm
(minimum)
Start
Unilift
430
AP35/50B
150 mm
(maximum)
Stop
Start
Stop
140
335
100
150
345
110
200 mm
(maximum)
Stop
Start
Stop
115
400
55
150
435
90
400 mm
(maximum)
Stop
Start
Stop
320
460
140
21