Descargar Imprimir esta página

Macurco CX-6 Manual De Instrucciones página 37

Ocultar thumbs Ver también para CX-6:

Publicidad

Idiomas disponibles

Idiomas disponibles

Macurco CX-xx Manual (Rev-1.0) Eng
7.3.2 Testing the Alarm Relay
1. Connect the gas cylinder to the regulator.
2. Check the pressure gauge. If there is 25psi or less the cylinder should be replaced.
3. Place the Calibration Hood over the sensor.
4. Turn on the regulator to start the gas flow. The Alarm Relay should activate according to the settings.
5. With the display function turned "On" and the gas concentration reaching the Alarm Relay setting, the
display will flash between "ALr" and "current gas reading". The buzzer will sound indicating "Alarm" if the
buzzer is turned "On". With the display function turned off the display does not show the gas concentration
but will show "ALr" when the Alarm Relay is activated.
Note: If the Alarm Relay fails to operate within 2 minutes, there are four possibilities:
a. Gas cylinder is empty. Check the pressure gauge. Replace the gas cylinder if 25-psi or less.
b. Unit needs to be re-calibrated (go through recalibration and re-test).
c. Detector needs servicing (return unit to factory for servicing).
d. The detector has the Alarm Relay set to disable ("diS") or a concentration level higher than the test
gas. Set the Alarm Relay to a gas concentration lower than the test gas and repeat the test.
6. Remove the gas from the sensor after Test. Proceed to Test the 4-20mA output or replace the top cover.
7.3.3 Testing the 4-20mA loop
1. Make sure the 4-20mA mode is set to "HigH" for this test.
2. Connect the gas cylinder to the regulator.
3. Check the pressure gauge. If there is 25-psi or less the cylinder should be replaced.
4. Place the cap from the regulator over the sensor. Turn on the regulator to start the gas flow.
5. The Fan relay should activate according to the settings.
6. The Alarm relay should activate according to the settings.
7. The 4-20mA output should ramp up from 4mA in clean air to 20mA at 200 ppm CO and 20mA at 20 ppm
NO
. See Figure 3–1 and Figure 3–2.
2
Note: If the 4-20mA output does not ramp up within 2 minutes, there are four possibilities:
a. Gas cylinder is empty, check the pressure gauge. Replace the gas cylinder if 25-psi or less.
b. Unit needs to be re-calibrated (go through recalibration and re-test).
c. Detector needs servicing (return unit to factory for servicing).
d. Detector has 4-20 mA option set to "OFF". Set 4-20mA option to "bAS" and repeat the test.
8. Remove the gas from the sensor. Re-assemble the CX-xx (make sure the LED is aligned with the front case
hole). You are done.
7.3.4 Aerosol Carbon Monoxide Test (Carbon Monoxide only)
The CME1-FTG is an 11L 500 ppm Aerosol Carbon Monoxide Field Test Gas that can be used with the CX-xx. This field
test gas allows installers to do a quick functionality test of the CO sensor. The flow rate of the CME1-FTG is 10 Lpm
so you will have about a minute of gas or enough to test 20-30 sensors.
1. Units to be tested must be powered continuously for a minimum of 3 minutes before proceeding.
2. For optimum test results the unit should be in clean air and be in a low ambient air flow.
3. Check that the CX-xx status indicator light is illuminated, Green continuously. If not, do not proceed with
tests. See section 5.1 On-Board Diagnostics.
4. The display option should be set to "On" and reading 0 ppm in clean air.
REV – 1.0
[34-2900-0512-0 ]
37 |
P a g e

Publicidad

loading

Este manual también es adecuado para:

Cx-12