injury or death. For proper use, see supervisor or user manual, or contact Technical
Support at 1-844-325-3050.
2.2 Do NOT use for
The CX-xx is not intended for use in hazardous locations or industrial applications such as refineries, chemical plants,
etc. Do not mount the CX-xx where the normal ambient temperature is below 0°F or exceeds 125°F (-18°C or above
52°C). The CX-xx mounts on a type 4S electrical box supplied by the contractor. Do not install the CX-xx inside
another box unless it has good air flow through it.
This equipment may not function effectively below 0°F or above 125°F (-18°C or above
52°C). Using the detector outside of this temperature range may adversely affect
product performance.
2.3 Features
ETL LISTED Certified to CSA C22.2 No 61010-1, Conforms to UL Std. 61010-1
Low-level meter capable of displaying from 0-200 ppm of CO and 0-20 ppm of NO
The CX-xx meets the Uniform Building Code for enclosed garages and meets OSHA standards for CO and NO
exposure
Selectable fan and alarm relay activation
5 A SPDT fan relay controls starters of exhaust fans
0.5 A N.O. or N.C. alarm relay connects to warning devices or control panels
4-20 mA Current Loop
CX-xx mounts on a standard 4x4 electrical box and becomes cover for the box
Supervised system: any internal detector problem will cause the fan & Alarm relay to activate
Calibration kit is available. One screw allows access for calibration or gas test
2.4 Specifications
Shipping Weight: 1 pound (0.45 kg)
Size: 4 1/2 x 4 x 2 1/8 in. (11.4 X 11.4 X 5.3 cm)
Color: White or Dark gray
Connections: plugs/terminals
Mounting box: (not included) 4x4 electric
Fan relay: 5 A, 240 VAC, pilot duty, SPDT, latching or non-latching
Fan relay actuation for CO: selectable at dIS (disable), 15, 25, 35 (default), 50 or 100 ppm
Fan relay actuation for NO
3.0, 3.2, 3.5, 3.7, 4.0, 4.2, 4.5, 4.7, 5.0 ppm
Fan Delay Settings of 0, 1, 3 (default), 5 and 10 minutes
Fan Relay Minimum Runtime settings are 0 (default), 3, 5, 10 or 15 minutes
Fan relay latching or not latching (default) selectable
Alarm relay: 0.5A 120 V, 60 VA
Alarm relay actuation: selectable N.O. (default) or N.C.
REV – 1.0
WARNING
: selectable at dIS (disabled) 0.5, 0.7, 1.0, 1.2, 1.5, 1.7, 2.0, 2.2, 2.5 (default), 2.7,
2
[34-2900-0512-0 ]