Descargar Imprimir esta página

Hitachi PC-ARFP1E Manual De Instalación Y Funcionamiento página 21

Ocultar thumbs Ver también para PC-ARFP1E:

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 85
TEST RUN MENU
Element
Optional function
Stop of indoor unit fan
during cooling thermo
OFF conditions
?
N O T E
Cd
For
model
FSN3E(P)E and RCD-
FSN3, this function is
NOT available.
Stop of indoor unit fan
during heating thermo
OFF conditions
Stop of indoor unit fan
CE
during heating thermo
OFF conditions (with
remote control switch
temperature sensor)
Modification of louvre
swing range
Models:
RCI-FSN4
RCIM-FSN4E
RCD-FSN3
RPC-FSN3
CF
Models:
RPK-FSN(H)3M
Management of indoor
unit operation after a
d1
power supply cut off -
option 1
Not available
d2
Management of indoor
unit operation after a
d3
power supply cut off -
option 2
13
PMML0496 rev.1 - 12/2020
Individual
Settings
setting
00
O
01
RPI-
00
O
01
00
01
02
O
00
01
02
00
O
01
"- -"
permanent
00
O
01
Setting conditions
Fan speed during cooling thermo
OFF: Low (factory setting)
Indoor unit fan is stopped during
cooling thermo OFF
Fan speed setting during heating
thermo OFF: Low (factory setting)
Indoor unit fan is stopped during
heating thermo OFF.
(In case that automatic louvre is
set, the louvres will keep operating
in both thermo ON and thermo OFF
conditions)
Standard (7 steps)
(factory setting)
Cold draft prevention (5 steps)
(Cannot be set to the lower two
steps; lower 2 steps cut off)
High ceilings (5 steps)
(Cannot be set the upper two steps;
upper 2 steps cut off)
Standard (7 steps)
(5 steps for cooling / dry mode)
Cold draft prevention
(5 steps for heating and fan only)
(Cannot be set to the lower two
steps, lower 2 steps cut off)
Not used
Function disabled
(factory setting)
Function enabled
Function disabled
(factory setting)
Function enabled
Description
The operation of the indoor unit fan
is stopped in cooling thermo OFF
conditions when using the additional
remote temperature sensor THM-
R2AE (connected to THM4) or the
PC-ARFP1E temperature sensor.
C8 must be set to 01 to use the
Cd=01 setting.
The indoor unit uses the PC-ARFP1E
temperature sensor to monitor the
room temperature when the fan is
stopped (heating thermo OFF fan
stop sequence)
C8 must be set to 01 to use the
CE=01 setting.
Control by remote temperature
sensor connected to THM4 is not
permitted (use E8 function in that
case).
This function adjusts the angle of the
air outlet louvre.
(Changes to the setting of this function
are applied after turning the power
supply off and on again, or after the
automatic louvre has made a full cycle
in automatic mode)
When power supply is restored, the
indoor units controlled by the wired
remote control switch are turned on
regardless of their ON/OFF status at
the time of the last power cut off.
When power supply is restored, the
indoor units controlled by the wired
remote control switch are turned
on automatically ONLY if they were
already ON at the time of the last
power cut off.
If indoor units were OFF when power
was turned OFF, they remain in OFF
status when power is restored.

Publicidad

loading