Descargar Imprimir esta página

Hitachi PC-ARFP1E Manual De Instalación Y Funcionamiento página 24

Ocultar thumbs Ver también para PC-ARFP1E:

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 85
TEST RUN MENU
Element
Optional function
Forced thermo ON when
stopping in cooling
EC
operation
Not used
Ed
Control in "Automatic"
EE
indoor fan speed mode
Control in "Automatic"
indoor fan speed mode
(supporting High H)
Models:
RCI-FSN4
RCIM-FSN4E
EF
RCD-FSN3
RPC-FSN3
RPI-FSN5E
RPI-FSN3E(P)E(-f)
RPIM-FSN4E(-DU)
RPK-FSN(H)3M
Not available
F0
Automatic OFF timer
setting
Models:
RCI-FSN4
RPC-FSN3
RPK-FSN3M
RPI-FSN5E
RPIM-FSN4E(-DU)
RCD-FSN3
F1
RCIM-FSN4E
RPI-FSN3(P)E
Automatic OFF timer
setting
Models:
RPF(I)-FSN2E
Remote control main-
F2
sub setting
16
PMML0496 rev.1 - 12/2020
Individual
Settings
setting
Function disabled
00
(factory setting)
O
Enabled
01
00
O
-
01
Function disabled
00
(factory setting)
O
Enabled
01
Function disabled
00
O
Function enabled
01
"- -"
permanent
Function disabled
00
(Factory setting)
1 hour
01
2 hours
02
3 hours
03
(04-24) hours
04-24
X
30 minutes
0A
90 minutes
0B
40 minutes
0C
45 minutes
0D
50 minutes
0E
55 minutes
0F
Function disabled
00
(Factory setting)
1 hour
01
2 hours
02
X
3 hours
03
(04-24) hours
04-24
30 minutes
0A
90 minutes
0B
Main (Master remote control)
00
(Factory setting)
X
Sub (Slave remote control)
01
Setting conditions
This function is used to force thermo
ON during 6 minutes when stopping
in cooling operation.
Use at 00 conditions
This function limits the speed of the
indoor fan when room temperature is
close to the setting temperature.
This function limits the speed of the
indoor fan when room temperature
is close to the setting temperature,
allowing to reach High H speed.
This function sets an automatic OFF
timer to switch OFF the indoor units
controlled by the remote control
switch (when the units have been
started by remote control).
}
(Do not set the values "0C"-"0F" when
two remote control switches are used
in the same remote control group)
Do not set these
when two wired
controllers are
used.
This function is used to set the
automatic timer to switch off when
the unit has been started by remote
control.
This function is used to define which
remote control switch is used as
master or slave, when two remote
controllers are connected to one
indoor unit.
Description

Publicidad

loading