3.3.4 Programming Field 3: CAN-Bus Protocols
chargers can communicate with the following CAN-Bus protocols:
O
3.4
PTIONS AND FEATURES
3.4.1 Bluetooth as a standard (Optional on OE version)
An optional Bluetooth dongle can be inserted easily in the user interface area.
The Cristec Connect Bluetooth application is available
on the Apple Store and Play Store allowing remote
wireless connection to the device, this application
allows monitoring and configuration of the device.
3.4.2 Thermal compensation (Optional)
STP-UNI-2.8 and STP-UNI-5.0 temperature probes enable the compensation of Absorption
voltage and Floating voltage depending on the ambient temperature of the battery room.
The coefficient used is -18mV/°C for 12V models and -36mV/°C for 24V models.
Temperature is not compensated when Wintering (or standby sealed bat), Stabilized DC
power supply or Lithium iron phosphate (LiFePO4) with BMS settings are selected.
3.4.3
OTD sensor (Optional)
input. This digital input stops the charging process and triggers an alarm if it remains open. This
feature complies with safety requirements such as hydrogen detection.
This input can be used as a remote ON/OFF using a dry contact.
By default, the function is inhibited by a jumper inside the charger.
To use this function, you must connect the OTD sensor to the front of
the device and move the jumper JP3 to position 1-2 in the user interface
area.
Settings
0
1
Factory setting
2
Bluetooth dongle
chargers are equipped with an OTD (over-temperature protection device) sensor
OTD connector on the front panel
Protocol
CRISTEC
Multibloc
PBUS
Jumper JP3
45