4. Instrucciones de funcionamiento
de la pantalla LCD
NO.
Item
Excessive discharge
–
delay time
Battery under voltage
14
alarm point
15
Battery discharge voltage limit
16
Downloading Equalization
17
EQ Discharge voltage
18
EQ Load Time
19
EQ download delay
20
Matching download interval
Equalization downloading
21
enable
22
Power Saving Mode
Overload automatic
23
restart
Configuration Options
[13] 5S Default
[14] 44V Default
[15] 40V Default
[16] DIS
[16] ENA non-compliance
[17] 58.4V Default
[18] 120 Default
[19] 240 unpaid
[20] 30 unpaid
[21] DIS
[21] ENA non-compliance
[22] DIS Default
[22] ENA.
[23] DIS
[23] Incumplimiento de ENA
79
Description
Over discharge delay time, when the battery voltage is
lower than parameter [12], the inverter output will be
turned off after delaying the time set by this parameter,
the adjustment range is 5S ~ 50S, step is 5S.
Low voltage alarm point of the battery, when the battery
voltage is lower than the judgment point, a low voltage
alarm shall be reported and the output shall not be
turned off. The adjustment range is 40V~52V, and the
step is 0.4V.
The discharge limit voltage of the battery, if the battery
voltage is lower than this judgment point, the output
shall be immediately switched off. Adjusting range
40V~52V, step 0.4V, valid when battery type is
customized and lithium battery.
Prohibited Equalization Fee.
Enable balanced charging, only valid for open lead acid
batteries and sealed lead-acid batteries and
custom batteries (User).
Balanced charging voltage, 48V~58.4V adjustment
range, 0.4V step, valid for open lead-acid battery and
sealed lead-acid battery, and valid for custom (user).
Equilibrium charging time, adjustment range
5min~900min, step 5min, valid for open lead-acid
battery and sealed lead-acid battery.
Balanced charging delay, 5min~900min setting range,
5min step, valid for open lead-acid battery and sealed
lead-acid battery and valid for user (user).
Balanced charging interval, 0~30 days, step 1 day,
valid for open lead-acid battery and sealed lead-acid
battery, and valid for custom (user).
Stop load equalization immediately.
Start matching the load immediately.
Disable power saving mode.
After enabling power saving moce, if the load is empty
or less than 50W, the inverter output will be turned off
after a delay for a period of time; when the load is
greater than 50WV, the inverter will start automatically.
Automatic overload restart is prohibited. If an overload
occurs, the output will be turned off and the computer
will not resume booting.
Enable automatic overload restart. If an overload occurs,
the output will shut down and the computer will restart the
output after a 3-minute delay. After accumulating 5 times,
it will not resume booting after a 3-minute delay. After
accumulating 5 times, it will not resume booting