Descargar Imprimir esta página

Kilsen KL710A Instrucciones De Instalación página 2

Ocultar thumbs Ver también para KL710A:

Publicidad

Idiomas disponibles

Idiomas disponibles

EN: Installation instructions
Installation
Caution:
For general guidelines on system planning, design,
installation, commissioning, use and maintenance, refer to the
CEN/TS 54-14 standard and local regulations.
To install a detector
Caution: Always recalibrate optical smoke detectors before
first-time installation.
1.
Insert the detector head into the mounting base and rotate
it clockwise until it clicks into place (Figure 1).
2.
The detector may be locked into the mounting base if
required. To do this, remove the locking tab before
installation (Figure 2).
3.
After installation, ensure that the detector communicates
with the control panel. If the detector does not
communicate with the control panel, check that duplicate
addresses have not been assigned.
4.
Always test detectors after installation.
To remove a locked detector
1.
Insert a small screwdriver into the locking tab slot (Figure
3).
2.
Press and rotate the detector anticlockwise.
Addressing
Each device requires a numeric address between 1 and 125
for identification purposes. This is assigned at the fire panel or
using a PG700 portable address programmer.
Maintenance
Basic maintenance is reduced to a yearly inspection. Do not
modify internal wiring or circuitry.
To replace the optical chamber (KL731A only)
1.
Remove the detector head from the mounting base.
2.
Remove the detector cover by pressing the catch with a
screwdriver, turning and lifting (Figure 4).
3.
Remove the existing optical chamber and insert the
replacement optical chamber (Figures 5 and 6).
4.
Replace the detector cover and install detector head into
the mounting base.
To clean the optical chamber follow the above instructions for
removal and use compressed air to clear the dust.
Caution: The detector must be recalibrated after cleaning or
replacement of the optical chamber.
Specifications
KL710A
Operating voltage
22 to 38 VDC
Current
Standby (38V)
250 µA
Alarm
< 11 mA
Pre-alarm indication
Flashing LED
2 / 8
KL731A
KL735A
22 to 38 VDC
22 to 38 VDC
250 µA
350 µA
< 11 mA
< 5 mA
Flashing LED
Flashing LED
KL710A
Alarm indication
Constant LED
Coverage
60 to 80 m
IP rating
IP42
Compatible mounting
KZ700, KZ705,
base
KZ705D
Temperature:
Operation
-10 to +60ºC
Storage
-10 to +70ºC
Relative humidity
10 to 95%
(noncondensing)
Colour
White
Dimensions (Ø × H )
99 × 45 mm
Weight
75 g
Certification and compliance
KL710A
Description
Heat detector
Variant
---
Certification
CPD certificate
1134-CPD-007
Year of manufacture
The year of manufacture is included in the first two
digits of your product serial number (located on the
product identification label).
EN 54
EN54-5
Class
A2
EMC
EN 50130-4
EN 61000-6-3
Manufacturer
Shanghai UTC Fire & Security Electronics, 1st
Floor No. 2 Building No. 211, Qinqiao Road Jinqiao
Export Processing Zone, Pudong New Area
201206, Shanghai, China
Authorized EU manufacturing representative:
UTC Fire & Security B.V.
Kelvinstraat 7, 6003 DH Weert, Netherlands
ES: Instrucciones de instalación
Instalación
Precaución:
Para información sobre el diseño, instalación,
uso y mantenimiento del sistema, aconsejamos seguir la
norma CEN/TS 54-14 y normas locales.
Para instalar el detector
Atención: Siempre recalibre los detectores ópticos antes de
su primera instalación.
1.
Inserte el detector en la base y girar en sentido horario
hasta que encaje perfectamente (Figura 1).
2.
El detector se puede bloquear en la base en caso de ser
necesario. Para ello, quitar la lengüeta antes de su
instalación (Figura 2).
3.
Tras la instalación, asegurar que el detector comunica con
la central. Si el detector no comunica con la central,
verificar que no tenga asignada una dirección repetida.
KL731A
KL735A
Constant LED
Constant LED
2
2
60 to 80 m
60 to 80 m
IP42
IP42
KZ700, KZ705,
KZ700, KZ705,
KZ705D,
KZ705D
KZ705R
-10 to +60ºC
-10 to +60ºC
-10 to +70ºC
-10 to +70ºC
10 to 95%
10 to 95%
White/Black
White
99 × 45 mm
99 × 51 mm
107 g
109 g
KL731A
KL735A
Optical smoke
Dual heat /
detector
smoke detector
KL731AB
---
1134-CPD-009
1134-CPD-012
EN54-7
EN54-5,EN54-7
---
A2R
EN 50130-4
EN 50130-4
EN 61000-6-3
EN 61000-6-3
P/N 55370159 • REV 2.0 • ISS 03OCT11