ELECTRICAL
Hazardous voltage . Can shock, burn, or kill.
Connect ground wire before connecting power supply wires. Use
the wire size (including the ground wire) specified in the wiring
chart. If possible, connect the pump to a separate branch circuit
with no other appliances on it.
Explosion hazard. Do not ground to a gas
supply line.
WIRING CONNECTIONS
FIRE HAZARD. Incorrect voltage can cause a
fire or seriously damage the motor and voids the warranty. The
supply voltage must be within ±10% of the motor nameplate
voltage.
Dual-voltage motors are factory wired for 230 volts. If
necessary, reconnect the motor for 115 volts, as shown. Do
not alter the wiring in single voltage motors.
Install, ground, wire, and maintain your pump in compliance
with the United States National Electrical Code (NEC) or the
Canadian Electrical Code (CEC), as applicable, and with all
local codes and ordinances that apply. Consult your local
building inspector for code information.
WIRING CHART – RECOMMENDED WIRE AND FUSE SIZES
FP4000, FP4100, 2800E, 3100P SERIES
MOTOR HP
VOLTS
LOAD AMP
1/2
115/230
8 .5/4 .3
3/4
115/230
11 .4/5 .7
1
115/230
12 .2/6 . 1
FP4150 AND 2200C SERIES
HORSEPOWER
VOLTS
1/2
115/230
3/4
115/230
1
115/230
8
BRANCH
MAX.
0-100 (0-30)
FUSE
RATING AMP
15/15
20/15
25/15
MAX.
BRANCH
LOAD
FUSE
AMP
RATING AMP
8 .5/4 .2
15/15
11 .0/5 .5
20/15
12 .0/6 .0
20/15
CONNECTION PROCEDURE
1.
Connect the ground wire first as shown in Figure 6. The
ground wire must be a solid copper wire at least as large as
the power supply wires.
2.
There must be a solid metal connection between the
pressure switch and the motor for motor grounding
protection. If the pressure switch is not connected to the
motor, connect the green ground screw in the switch to the
green ground screw under the motor end cover. Use a solid
copper wire at least as large as the power supply wires.
3.
Connect the ground wire to a grounded lead in a service
panel, to a metal underground water pipe, to a metal well
casing at least ten feet (3 m) long, or to a ground electrode
provided by the power company or the hydro authority.
4.
Connect the power supply wires to the pressure switch as
shown in Figure 6.
DISTANCE IN FEET(METERS) FROM MOTOR TO SUPPLY
101-200 (31-61)
AWG WIRE SIZE (MM
14/14 (2/2)
12/14 (3/2)
14/14 (2/2)
10/14 (5 .5/2)
12/14 (3/2)
8/14 (8 .4/2)
DISTANCE IN FEET(METERS) FROM MOTOR TO SUPPLY
0-100 (0-30)
101-200 (31-61)
AWG WIRE SIZE (MM
14/14 (2/2)
12/14 (3/2)
12/14 (3/2)
10/14 (5 .5/2)
12/14 (3/2)
10/14 (5 .5/2)
201-300 (62-91)
301-400 (92-122)
)
2
10/14 (5 .5/2)
8/14 (8 .4/2)
8/14 (8 .4/2)
6/12 (14/3)
8/14 (8 .4/2)
6/12 (14/3)
201-300 (62-91)
301-400 (92-122)
)
2
10/14 (5 .5/2)
8/14 (8 .4/2)
8/14 (8 .4/2)
6/14 (14/2)
8/14 (8 .4/2)
6/14 (14/2)