Regulador de corriente constante tipo tiristor (CCT) L-828 y L-829 enfriado por aire
Diagramas
Figura 41:
Diagrama del cableado interno del CCR L-828 y L-829 CCT (tipo tiristor) (Parte 2 de 2)
J2/J3 WIRING DETAIL ENLARGED
9/572
J2
1
2
3
4
5
6
7
8
3 STEP ONLY
501
531
10=15,20,30KW; 573=4,7.5,10KW
9=15,20,30KW; 572=4,7.5,10KW
8=15,20,30KW; 571=4,7.5,10KW
6=15,20,30KW; 570=4,7.5,10KW
7.5KW, SCR 28A0039,
208-480V (NO GND WIRE)
G1
G2
K1
K2
15KW, SCR 28A0034,
208-480V (NO GND WIRE)
K1
G1
G2 K2
DETAIL"A"
OPTIONAL
208
SCO
TO
AIRFIELD
209
70A0279 TERM.
(2 PLC.S)
70A0596;
MALE FASTON
TERM.
REPLACE FORK TERM.
ON HARNESS W/FEM.
FASTON TERM.
ADD 72A0019
FORK TERM.
70A0279
66
96A0296 Rev. P
DIGITAL POWER METER OPTION
OUTPUT NOTE:
J3
OUTPUT CONNECTIONS
200
ON VR1AND VR2 UNLESS
TERMINAL BLOCKS OR
537
220
"SCO" IS USED.
SEC.
PRIM.
1
2
3 4 5
6 7 8
536
901
T7
216
216
VR1
202/203
202/203
207
T6
VR2
6.6A = 35A0493
20A = 35A0528
VR4
VR3
(NOTE 3, PG. 2: PROD. ONLY)
VR6
VR5
800
801
590 (TB1-CCI-120)
120V
591 (TB1-NEU)
TB2
TB3
CLOSED @
TB1
RELAY/LOAD_SELECT
CONNECTIONS TO DPM
10KW, SCR 28A0038,
PREVIOUS SCR WIRING
208-480V (NO GND WIRE)
7.5KW, SCR 28A0039,
10KW, SCR 28A0038,
208-480V (NO GND WIRE)
208-480V (NO GND WIRE)
K1 G1
G2
K2
K1
G1
G1
G2
K1
K2
20 & 30KW, SCR 28A0041,
20 & 30KW, SCR 28A0041,
(ALSO 28A0028),
(ALSO 28A0028),
15KW, SCR 28A0034,
208-480V (NO GND WIRE)
208-480V (NO GND WIRE)
208-480V (NO GND WIRE)
K1
G1
G2
K2
4K
K1
K2
5G
G1
G2
PREVIOUS IRMS W/RES WIRING
PREVIOUS "MOLDED" STYLE CVM WIRING
(SEE PG. 2 WIRE NO.S)
IRMS
605
ACE Potted CVM/IRMS Options
F6
529
Use wrench to hold RES when
530
attaching wires
CVM
TB1-L2
(T2/T3 and meter not used)
216
(200 W/O IRMS; 201 W/IRMS)
Use wrench to hold RES when attaching wires.
5/15/12
100 SERIES WIRES - PRIMARY POWER - 600V - 105°C
POWER
208 V
220 V
230 V
240 V
14AWG
14AWG
14AWG
14AWG
4 kW
89A0184/9
89A0184/9
89A0184/9
89A0184/9
8AWG
8AWG
8AWG
8AWG
7.5 kW
89A0196/9
89A0196/9
89A0196/9
89A0196/9
8AWG
8AWG
8AWG
8AWG
10 kW
89A0196/9
89A0196/9
89A0196/9
89A0196/9
ATTACH "OUTPUT" TAG - 2 PLC.S
4AWG
4AWG
4AWG
6AWG
15 kW
TB2
89A0198/9
89A0198/9
89A0198/9
89A0197/9
206
212
1
1/0AWG
1/0AWG
1/0AWG
2AWG
20 kW
TO
89A0201/9
89A0201/9
89A0201/9
89A0199/9
AIRFIELD
1/0AWG
1/0AWG
1/0AWG
2AWG
30 kW
207
213
2
89A0201/9
89A0201/9
89A0201/9
89A0199/9
ALT.,7.5KW, 240V, 35C0197 CORE
ALT., 15KW, 240V, 35A0291 CORE
TB6
T1
600
1
TB5
1
IF VARISTORS ARE PLATE MOUNTED,
1
5
GND PLATE TO EARTH GND.
3
104
2
1
3
7
4
CT
EARTH GND
C.T.
6
5
4
2
6
7
8
8
2
601
108
2
DIGITAL POWER METER
44A6528
OPTIONAL INPUT CVM PCB
(-V)
542
J5
DANGER: HIGH VOLTAGE
G2
LETHAL VOLTAGES ARE PRESENT
K2
543
J2
(+V)
ICVM PCB
NO POLARITY
44A6626
J3
J4
U12
FIBER OPTIC
3
1
2
CABLE
1
F6-529
TB1-N:530
TB1-GND:909
K2
7K
F1
102
6G
1
2
F2
103
103
3
4
105
5
6
A1
A2
CCT CONTROL
PCB
9/572
1 2
F5
501
TB1-N
531
TB1-GND
216
NOTES:
1. WIRE SIZES:
347 & 400V-50Hz
480 V
2400 V
100-113: PRIMARY POWER, SEE TABLE.
14AWG
14AWG
89A0184/9
89A0184/9
200-217: HIGH VOLT., 12AWG, 25KV, SIL, 89A0086/1.
8AWG
14AWG
400-403: MEDIUM CURRENT, 12AWG, 600V, 89A0185/9.
89A0196/9
89A0184/9
500-560: STD CONTROL, 18AWG, 600V, 89A0182/9.
8AWG
14AWG
89A0196/9
89A0184/9
600-: HI-VOLTAGE, 8AWG, 7.5KV, 89A0202:
6AWG
10AWG
OBSOLETE - USE "200" SERIES WIRE.
89A0197/9
89A0195/9
751-759: SMR, 22AWG, 2 COND. W/SHLD, 89A0126.
2AWG
6AWG
89A0199/9
89A0197/9
800-804: GROUND, 12AWG, 600V, GN/YL, 89A163/5.
2AWG
6AWG
900-905: GROUND, 18AWG, 600V, GN/YL, 89A0163/7.
89A0199/9
89A0197/9
2. SEE BILL OF MATERIALS FOR NUMBER OF MOV's OR
SURGE SUPPRESSORS IN EACH LEG.
3. IF 6.6A REGULATOR IS WIRED W/O METER, LAND 507 ON
J5-1 IN PLACE OF 505.
TB6
4. IF 20A REGULATOR IS WIRED W/O METER, LAND 205 ON
T1
TB5
5
5
T3-S2 IN PLACE OF 203.
5
1
600
3
3
104
3
5. IF A JUMPER IS NEEDED FOR ANY CORE LEAD, USE HIGH
1
2
1
VOLTAGE 89A0086/1 WIRE.
3
1
7
4
6. DELETED REV. U.
CT
C.T.
6
5
7. ROUTE THESE WIRES SEPARATE FROM CONTROL WIRING.
4
2
2
6
2
8.
TORQUE ALL CONTACTOR CONNECTIONS PER CONTACTOR
7
4
601
PRODUCT LABEL.
4
8
8
6
108
6
44A6313/1-/2
CCT WIRE HARNESS, SM. & MED. FRAME
44A6314/1-/2
CCT/ACE WIRE HARNESS, SM. & MED. FRAME
POWER WIRE KIT, CCT CCR
94A0349/XXXX
43A2855
WIRING DIAGRAM, ACE1 TO CCT CONTROL PCB
43A3129
WIRING DIAGRAM, ACE2 TO CCT CONTROL PCB
DOC. NO.
DESCRIPTION
RELATED DOCUMENTS
FOR 380V, 60HZ WIRING,
SEE 43A3982.
S1
J1B
PIN
1
OPTIONAL SMI & SMR
TB1
WIRING
J3
538
14
4
3
4
5
6
7
8
KS1
901
565
120VAC
548
547
8
12
13
KS1
TBS4
562
550
14
4
547
7
KS2
549
548
561
12VDC
8
12
8
13
KS2
549
9
4
550
10
552
551
551
11
8
12
552
557
12
3
553
13
7
11
564
14
554
558
14
2
KS3
555
553
15
12VDC
6
563
10
556
13
KS3
16
558
4
12
554
8
540
13
3
557
KS4
555
7
120VAC
556
11
539
KS4
14
PRIMARY
>
POWER
INTERNAL
>
REMOTE
COMMAND
>
ON
>SAMPLING
SAMPLE
>
GATE
© 2010 ADB Airfield Solutions Todos los derechos