A&E Specs
Performance Requirements
Unit's blower shall be designed to maintain a constant airfl ow in typical installations
Noise level shall be lower than 0.65 sone at 130 CFM, 0.2 in w.g.
Unit speed shall be selectable from 30 to 180 CFM in 10 CFM increments.
Backdraft damper shall have a magnet to prevent fl ickering and stay closed during door blower test.
Unit's blower effi ciency shall be at least 8.3 CFM/W at 120 CFM, 0.2 in. w.g.
Unit shall be equipped with test ports to allow airfl ow measurement.
Unit shall have an access door that allows quick and easy maintenance of all parts.
Construction Requirements
Blower wheel shall be metallic.
Unit shall have an ECM motor.
Backdraft damper shall be integrated to the unit.
The unit's blower shall be protected by a grill.
Filter shall be accessible without a tool.
Unit's housing and door shall be paintable and made of 24 ga galvanealed steel.
Unit shall include a washable metallic fi lter.
Unit shall allow 2-in. thick MERV fi lters in option.
Unit shall be equipped with a power cord at least 5.5-ft long with NEMA 5-15P and an integrated strain relief.
Unit's width shall not exceed 10.25".
Unit's height shall not exceed 10".
Unit's housing's length shall not exceed 14.75".
Unit's weight shall not exceed 12 pounds.
Quality Requirements
All plastic parts in the airfl ow shall be UL94 HB fi re rated.
Electrical enclosure shall be in plastic to prevent condensation and UL94 5VA fi re rated.
Unit's housing shall be insulated and not show any thermal bridge to the metallic housing.
Unit's insulation shall be made of expanded polystyrene and UL94 HF-2 fi re rated.
Unit shall be protected by a 5-year warranty.
Unit shall be HVI rated.
Unit shall be ASHRAE 62.2 2010 and 2016 IRC/IMC compliant.
Unit shall be certifi ed by an independent laboratory.
Manufacturer shall be ISO 9001-2015.
Manufacturing plant shall be located in North America.
Installation requirements
Unit shall fi t between 12-in. cc joists.
Unit shall be designed to be connected with central ventilation or to be used in a standalone installation.
Unit shall be suitable for ceiling hung, ceiling mounted, attic mounted, wall mounted and fl ush-to-ceiling installation.
Unit shall be designed to be installed in any orientation.
Unit's ports shall be 6-in. round with bumps to maintain a tie-wrap in place.
FIN-180Bd180427