TYPE OF RISKS
Safety and reliability of the dri-
ve group and of the command
and safety devices.
Safety conditions in the event of
a breakdown and failure of the
power supply.
Start-up and stop of the drive
group.
Power switch.
Consistency of the commands.
Enclosure risks.
Emergency stop.
Principles of integration of secu-
rity and information.
Signals.
Maintenance.
Residual risks.
The technical characteristics and performances of the components mentioned below are documented in the respective installation
manuals or in the label on the component.
Drive group/motor:
Control unit:
Radio device:
EVALUATION CRITERIA AND SOLUTIONS TO ADOPT
*Use drive groups conforming to EN 12453 and safety devices in compliance with
EN 12978.
*Check that the door does not make dangerous movements (in case of breakage
system suspension, the door should not fall more than 300 mm).
*Check that after a breakdown or a power failure, the drive group resumes the operation
safely, without creating dangerous situations.
*Install an omnipolar switch for electrical insulation of the door, according to
current regulations. This switch must be installed and protected from involuntary or
unauthorized activations.
*Install the commands (for example the key switch) in such a way that the user will not
find in a dangerous area and verify that the user understands the meaning of
the commands (for example the function selector).
*Use radio controls with CE mark and in accordance with the frequencies admitted in
every country.
*Install a release device for unlocking the automation that permit you open and close
manually the leaf with a maximum force of 225 N.
Provide users a means and instructions to release the automation, check that the device
has easy operation and do not generate additional risks.
*If appropriate, install an emergency stop command.
*IMPORTANT: Check that the emergency stop does not create new risks, verifing
the functioning of safety devices installed.
*Apply all necessary signs or warnings to indicate residual risks and potential
non-compliant uses.
*A maintenance plan must be established and performed. Check every 6 months as
minimum that the safety devices work correctly.
*Inform users about the presence of residual risks and the potential inadequate use.