BRAUKMANN FK06 DIALSET®
Table 1. Rinsing Quantity.
Filter size
3/4"–1 1/4"... 101-103 6.6 gallons
* at 58 psi (4 bar) inlet pressure and a rinse
duration of 15 seconds
COMMISSIONING
Setting outlet press
Changing the Downstream
Pressure(See Fig. 2)
Remove the dust cap from the FK06. The
FK06 is factory set to 60 psi.
To adjust the outlet pressure to a desired
setting:
1. Loosen the locking screw by turning
counter-clockwise
remove this screw.)
2. Turn the adjusting knob counter-clock-
wise
to reduce pressure or clock-
wise
to increase pressure.
3. Lock the setting by turning the locking
screw clockwise
4. Replace the dust cap over the dial.
38-00059EFS—11
C in in.
Rinsing quantity*
(mm)
3/4
(25 liters)
(20)
(Do not
.
ADJUST SETPOINT AT THE DESIRED VALUE BY ACTUATING SELECTOR.
INLET PRESSURE (MAXIMUM): 250 PSI
REDUCED PRESSURE RANGE:
25 TO 90PSI 3/4 IN. TO 1-1/4 IN. SIZE
NOTE: DO NOT DISMANTLE
KNOB
SET-POINT READOUT HAS BEEN
CALIBRATED IN THE FACTORY AND SET
AT 60 PSI. DISMANTLING THE SELECTOR KNOB
WILL CANCEL THIS CALIBRATION. RECALIBRATE
USING A PRESSURE GAUGE. SEE RECALIBRATION.
Fig. 2. Changing outlet pressure.
MAINTENANCE
We recommend a planned maintenance
contract with an installation company.
Inspection
Filter
Frequency: at least every 2 month (depending
on local operating conditions.
• Non-compliance can lead to the filter
becoming blocked This results in a drop in
pressure and decreasing water flow
• The filter meshes are made of stainless
steel. A red coating as a consequence of
rust from the pipelines has no influence on
function or the way the filter works
To be carried out by an installation company
or the operator.
NOTES:
—
Filtered water can be drawn
during rinsing.
—
If rinsing is into a container, then
a suitable container must first be
put underneath.
4
LOOSEN LOCKING
SCREW ONE TURN
M36657A