Troubleshooting
THE OUTLET FLUID
TEMPERATURE
EXCEEDS THE SET
VALUE
no
EXCESSIVE
FLUID
FLOW, HIGH
THERMAL LOAD
yes
REDUCE THE FLOW
RATE OF THE WATER TO BE
COOLED
HIGH
AMBIENT
TEMPERATURE
yes
RETURN THE
AMBIENT
TEMPERATURE TO BELOW
THE
SPECIFIED LIMIT
FAULT
COMPRESSOR STOPS DUE
TO OPERATION OF THE HIGH
PRESSURE SWITCH
PRESSURE SWITCH
BROKEN OR
WRONGLY
CALIBRATED
yes
REPLACE
PRESSURE SWITCH
no
CONDENSER
FINS
DIRTY
yes
CLEAN THE FINS
OF THE
CONDENSER
ICEP002-005
REMEDY
CAUSE
COMPRESSOR SUCTION,
LIQUID LINE
FROSTED UP
REFRIGERANT
INSUFFICIENT
FILTER
FLUID FLOW
CLOGGED
yes
yes
INCREASE THE
FLOW RATE OF THE
REPLACE
FLUID TO
THE FILTER
BE COOLED
no
CONDENSER SURFACES
CLOGGED
yes
CLEAR THE FRONT
SURFACE
OF THE
CONDENSER
COMPRESSOR
RUNS FOR
LONG PERIODS,
NOISY
COMPRESSOR
COMPONENTS
DETERIORATED
yes
REPAIR OR
REPLACE
COMPRESSOR
no
LEAKS IN
REFRIGERANT
CIRCUIT,
FILTER
SYSTEM
CLOGGED
DISCHARGED
yes
yes
CHECK
REPLACE
FOR LEAKS,
THE FILTER
ELIMINATE THEM, CHARGE
THE CIRCUIT