INSTALLATION INSTRUCTIONS
* NOTE: Product installation details with OCPP1.6J service agreement. Refer to "Network Connection guide". **
NOTE: Product installation details with power management. Refer to "Power management function installation
guide".
1. Drill holes according to fig. 1**.
2. Use the accessory sealing rubber to fix the CT wire.
3. Insert the sealing part into the housing body, as fig. 8, thread the CT wire into the sealing part, one hole
corresponds to one CT wire, after the CT cable is inserted, reserve enough length to connect to the CT
interface;
4. Crimp the CT wire to the CT wire terminal and then insert it into the CT interface, as following fig. 2**
5. Open the CT and fixed it to the main incoming line (one CT is only allowed to pass through one line).
φ18mm
100mm
fig. 1**
If you need to connect new energy sources such as solar energy, you can refer to the following figure for
installation:
CT1:Supply grid
balancing interface
CT2: Solar energy
balancing interface
B-Black
R-RED
SUPPLY
ELECTRIC
GRID
METER
According to the diagram, put the CT of the supply grid balance on the L line of the family main line. The
1.
direction of the arrow on CT must be the same as that of the arrow shown in the diagram, the red line of CT is
positive 2, and the black line is negative 1. press it to the matching terminal CT1.( Pay attention to check that
the CT interface base on PCB is marked with CT1.)
According to the diagram, the CT of the solar balanced load is sheathed on the L line of the inverter output
2.
AC 230V. The direction of the arrow on the CT must be the same as that of the arrow shown in the diagram,
the red line of CT is positive 4 and the black line is negative 3, press it to the matching terminal CT2. (Pay
attention to check that the CT CT interface base on PCB is marked with CT2.)
Power management function installation guide
CT1 CT2 CT3
B R B R
B - Black
R - Red
Cable crimp to terminal plug
B
1
2
R
3
B
4
R
5
6
CONSUMER
UNIT(S)
Plug into CT interface.
CT1
CT2
CT3
FIT
METER
11
CT opening and
closing after the
insertion of the line,
the CT is firmly fixed.
INVERTER
SOLAR ENERGY
fig. 2**
V.1