FireClass
Technical specification
Type Identification
Value
System
Compatibility
Environment
Operating
Temperature
Storage
Temperature
Operating Humidity
Dimensions
(HxWxD)
Mounting
Requirements
Recommended Wire
Size
Battery requirements
Standby current
Alarm current
Addressable device
Conditions:
Input Circuit
EOL
Alarm resistor
Fixing instructions Doc. version 5.0
148
Use only with FC
Fire Alarm
Controllers
Indoor Application
only
-25 °C to +70°C
-40 °C to +80°C
Up to 95% non-
condensing
85 × 60 × 15 mm
Dual-gang
electrical box
2
Min. 1.5 mm
,
2
Max. 2.5 mm
0.3 mA
3.0 mA
– Normal
– Active
– Short Circuit wiring
fault
– Open Circuit wiring
fault
– Device Type Invalid
– Device No Response
3K3
680 ohm
ENGLISH
Electromagnetic compatibility
The FC410SIO complies with the following:
product family standard EN50130-4 in respect
of Conducted Disturbances, Radiated Immu-
nity, Electrostatic Discharge, Fast Transients
and Slow High Energy;
EN61000-6-3 for emissions.
Introduction
The FC410SIO Single Input/Output Module is
designed to provide a monitored open collector
input and a volt free relay changeover output.
Features
FC410SIO can switch up to 2 A @ 24 Vdc
Wiring & installation notes
The following notes apply:
1 There are no user-required settings (such as
switches or headers) on the FC410SIO.
2 All wiring must conform to the applicable
standards.
3 All conductors to be free of earths.
4 Verify the correct polarity of wiring before
connecting the FC410SIO to the addressable
loop circuit.
5 For FC410SIO typical wiring configuration see
Fig. 4.
Installation to FC470CV ancillary
cover
1 Assemble the FC410SIO to FC470CV anci-
llary cover, using the four screw and washers
provided.
2 Fit cover onto dual-gang backbox.
Address settings
The FC410SIO has a default factory set address
of 255, this must be set to the loop address of
the device using the FC490ST Loop Service
Tool. The FC410SIO may be programmed with
the address prior to being installed by using the
internal programming port (see Fig. 2) or after
FC410SIO