5. Commissioning, operation
5.3.2 Programming the display
1. Connect instrument in accordance with connection diagram.
2. Switch on the current-loop supply (current between 4 ... 20 mA).
An initialisation and segment test is carried out. Then DIH10-Ex and
EN
subsequently the firmware version number (e.g. F1.24) is displayed.
Following this, the display switches into operating mode.
3. Press the program button P, the program number P 0 will be
displayed.
4. By pressing P and the
change the program number.
5. Under the selected program number, switch to the stored value with
the P button.
6. By pressing P briefly, the required digit can be selected. The selected
digit is changed using
7. The entry is saved by pressing the P button for approx. 2 seconds; the
value has been saved once the display shows horizontal bars.
8. If no button is pressed, after approx. 7 seconds the instrument returns
to operating mode.
Additional functions in normal operation to retrieve the recorded
Min/Max values
Using the
■
in the display for some seconds.
Using the
■
in the display for some seconds.
By simultaneously pressing the
■
values are deleted.
If the measuring range setting is changed, to maintain the measurement
accuracy, the display must be recalibrated.
20
button or P and
or
button, the recorded value of the Max memory is shown
button, the recorded value of the Min memory is shown
WIKA operating instructions model DIH10-Ex
button simultaneously,
.
and
buttons, the Min and Max