If DIP 6 is set to OFF = > it opens the closed gate. If operated while the gate is opening, the
button has no effect. If operated with the gate open, it closes the
gate. If operated while the gate is closing, it re-opens the gate.
PEDESTRIAN OPENING BUTTON (COM A+/PED.)
Command reserved to partial opening and re-closing of the gate.
When opening, closing or pausing the pedestrian command, you can control the full opening
using any command connected on the board.
Using the DIP switches 6, you can choose the operating mode of the pedestrian control
button.
If DIP 6 is set to ON = > it runs a cyclical command sequence open-stop-close-stop etc.
If DIP 6 is set to OFF = > it opens the closed gate. If operated while the gate is opening, the
button has no effect. If operated with the gate open in pedestrian
mode, it closes the gate. If operated while the gate is closing, it
re-opens the gate.
MANUAL RELEASE (LED DL16)
The position of the unlocking lever is controlled electronically, so if you unlock the operator,
the microswitch contact will open (led DL16 turns off) and the controls are not enabled.
When you reposition the release lever, and after running a command, the first
movement will take place at slow speed. Only after completing this first movement,
the operator will resume work at the set speed.
OPERATION OF SAFETY DEVICES
PHOTOCELL (COM A+/PHOT) - Safety function PL "b" according to EN13849-1
With the photocell enabled, the buzzer emits 1 tone.
DIP 4 OFF = > with gate closed, if an obstacle stops the photocell beam, even if an opening
command is given, the gate does not open. During operation, the photocells
intervene both during opening (with the gate opening only after freeing the
photocell beam), and closing (with reverse motion recovery only after freeing
the photocell beam).
DIP 4 ON = > with the gate closed, if an obstacle is in front of the photocell beam and
the control to open the gate is operated, the gate opens (during opening
the photocells will not intervene). The photocells will intervene only during
closing (with the gate opening after 1 second, even if the photocells are
still engaged).
ATTENTION: In case the receiver led remains lit, malfunctioning of the main supply
is suspected.
It is advisable to connect electrically to earth the
columns or the photocells stands to the terminal A -, to
shield the photocells from external noise.
Be careful not to short circuit the system when the
supply phases are inverted!
PHOTOCELLS "AUTO-TEST" MONITORING (A+/A- TEST)
Connect the photocell transmitter to A+ TEST/A- and set DIP 7 to ON.
The monitoring consists of a functional test of the photocell run before every movement.
The gate movement is therefore permitted only if the photocells have passed the functional
test.
CAUTION: MONITORING OF THE PHOTOCELLS INPUTS (PHOTO 1/PHOTO 2) CAN BE
ACTIVATED WITH DIP 7 ON OR DEACTIVATED WITH DIP 7 OFF.
WARNING: If the AUTOTEST feature is enabled and only one photocell is connected,
a jumper must be made between the PHOT 1 and PHOT 2 terminals. If
the jumper is not made, the AUTOTEST fails and the gate will not move.
FAILED AUTO-TEST ALARM (DIP 7 ON)
If the photocell fails the monitoring test, an alarm is displayed by the blinker lighting up
and gate movement is not allowed. Normal operation can be restored only by repairing the
photocell and pressing one of the controls.
EDGES (SAFETY STRIPS) (COM A+/EDGE 1/EDGE 2) - Safety function PL "b" according
to EN13849-1
If engaged when closing, EDGE 1 reverses the motion in opening. If edge remains engaged,
it doesn't permit the closing.
If engaged during opening, EDGE 2 reverses the motion in closing. If edge remains engaged,
it doesn't permit the opening.
If edges are not used, jump the terminals COM A+/EDGE1/EDGE2.
The movement will restart at a slow speed until the opening or closing limit switch is reached.
EDGE ALARM
Flasher and buzzer are activated with 2 tones every 5 seconds for one minute.
STOP BUTTON (COM A+/STOP) - Safety function PL "b" according to EN13849-1
During the movement, the stop button will stop the gate.
If the STOP button is pressed when the gate is fully open (or partially using the pedestrian
command) the automatic closure will be temporarily excluded (if enabled via trimmer ACT
with led DL11 ON). It is therefore necessary to give a new command to close the gate.
Closing the gate will re-enable automatic closing (if enabled via trimmer ACT with led DL11
ON).
HEATER FUNCTION (DIP 13 - ON)
Allows the operator to always operate at a temperature suitable for the operation.
This device automatically turns on only when the gate is at a standstill and the opening or
closing limit-switch engaged, at an ambient temperature of the motor of 0° C, detected by
the sensor mounted on the board.
When the motor is in motion, the heater is turned off.
After 10 seconds that the gate remains stationary, the heater is activated (if the motor
ambient temperature is less than or equal to 0° C).
When the motor reaches a temperature of 3° C, the heater shuts down, maintaining the
environmental conditions at a constant temperature.
VISUAL AND SOUND ALARMS
FLASHER
IMPORTANT: This electronic panel can power only one flasher with flashing circuit (ACG7061)
PRE-FLASHING FUNCTION
DIP 5 - OFF => the motor and flasher start simultaneously.
DIP 5 - ON => the flasher starts 3 seconds before the motor.
BUZZER
Signals that the safety devices have triggered an alarm, alarm status and codes saved/
deleted in memory.
GATE OPEN 24Vdc INDICATOR LIGHT (COM A+/SIGNAL -)
The light signals that the gate is open, partly open or not completely closed. Only when the
gate is completely closed does the light turn off.
During opening, it flashes slowly.
24Vdc
When the gate is stationary or opened, it is permanently on.
Term.
During closing, it flashes quickly
A -
N.B.: Max 3 W. If warning lights are in excess, the control panel processes will be
endangered with possible stop of all operations.
OPERATION AFTER BLACK-OUT (WITHOUT BATTERIES)
At the time of the blackout, gate status is saved in the memory.
When mains voltage is restored:
If the gate is located on the opening or closing limit switch, operating the control will close
or open the gate with the saved data.
If the gate is in intermediate position, operating the control will open the gate slowly until
it reaches the opening limit switch. After completing this first movement, the operator will
resume work at the set speed.
TECHNICAL SPECIFICATIONS
- Temperature range
- Humidity
- Power supply
- Frequency
- Transformer power
- Maximum absorption
- Power supply microinterruptions
- Maximum power SIGNAL output
- Flasher maximum load
- Current available for photocells and accessories 24Vdc 500 mA ±15%
- Battery power supply
RADIO TECHNICAL SPECIFICATIONS (model L1 24V-CRX)
- Reception frequency
26
with a 24 V and 3 W (maximum) lamp. If you exceed 20 W, the electronic
panel's logic will be compromised, with the system possibly stopping.
-10 ÷ +55°C
< 95% without condensation
230V~ ±10% (120V 60Hz on request)
50/60 Hz
150VA - main 230Vac
1st secondary 24Vac
2nd secondary 10Vac
130 mA
100ms
24 Vdc 3 W
24 Vdc 20 W
24Vdc
433,92MHz