TROUBLESHOOTING
After making all the connections, carefully following the diagram and having placed the gate in intermediate position, check the correct lighting of led DL4, DL5, DL6, DL7, DL8, DL9, DL10
and DL16.
If one of the led does not turn on, check the following and replace any faulty components if necessary (perform the inspection with the gate always in intermediate position):
DL4 red off - limit switch that stops gate closure is faulty
DL5 green off - limit switch that stops gate opening is faulty
DL6 red off - stop button fault (if the STOP is not connected, run the jumper between COM and STOP).
DL7-8 red off - photocell fault (if the photocells are not connected, run the jumper between COM and PHOT 1/PHOT 2).
DL9-10 red off - safety edge fault (if the edge is not connected, run the jumper between COM and EDGE 1/EDGE 2).
LED DL13 (BLUE)
ON
DL16 red off - manual release open (close it to restore the operation)
During operation, hold DIP 1 in ON position, make sure that when the gate opens, the green led DL2 turns on and that when the gate closes, red led DL3 turns on.
Otherwise, perform a new full opening programming sequence.
On the board there are resettable fuses which intervene in the event of a short circuit, interrupting the output assigned to them.
In the event of troubleshooting, it is advisable to disconnect all the removable connectors and insert them one at a time in order to more easily identify the cause of the fault.
After making the various connections and supplying voltage, all leds are off.
The photocells are not lit and the motor does not rotate
The gate opens, but does not close after the set time
The gate does not open and does not close when pressing the various OPEN-CLOSE-START-
RADIO buttons.
When the gate is open, pressing the START, RADIO button or the CLOSE button, the gate does
not move.
the gate triggers an alarm due to over-current, signalled by 3 buzzer tones.
LED DL1 flashes ON-OFF 250ms.
When programming the time, the gate stops and the buzzer emits a tone for 10 s, with pause
for 2 s.
Impact sensor intervenes during the movement
The buzzer emits 2 long tones and the gate does not move
The remote control does not work. Led DL12 lit red
Some functions are enabled via smartphone, so via smartphone check the card functions as the dips/trimmers status may not be true.
PROBLEM
On the board there are resettable fuses which intervene in the event of a short circuit,
interrupting the output assigned to them.
In the event of troubleshooting, it is advisable to disconnect all the removable
connectors and insert them one at a time in order to more easily identify the cause of
the fault.
Check the integrity of fuse F1.
In case of faulty fuse, replace it only with one of the same value: F1 = T 1,6A
Check the integrity of fuse F2.
In case of faulty fuse, replace it only with one of the same value: F2 = T 10A
Check that led DL11 turns on. If it is off, turn the trimmer clockwise.
Or, check that the photocells are not engaged.
It is also possible that you have pressed the STOP button with the gate open, temporarily
blocking the automatic closure.
Stop, Edge or Photocell with DIP 4 OFF contact fault. Fix or replace the faulty contact.
Or, check that manual release device is not open.
Clock function enabled. Check the status of the B.I.O. input.
Or, photocells auto-test failed = > check the connections between the electronic panel and
photocells.
Check the sliding of the gate, making sure that there is no friction. Only if necessary, set DIP
7 to OFF to exclude the impact sensor.
DIP 1 set to ON. Set it to OFF.
Or, an edge or photocell is broken. The movement is allowed only by hold-to-run command.
Incorrect programming sequence. Set DIP 2 to OFF.
Bring the gate at about 20 cm from the end closure and repeat the programming sequence.
Turn the SENS trimmer clockwise
Safety edge with 8,2 KΩ resistor. Remove the resistor or configure the EDGE input via the
RIB GATE app
Lack of radio module in connector J6 or faulty radio module.