1.3 Variations in the range of use
Range of
Parameter
influence
Temperature
-10...+60°C
Relative humidity
10...90%
Conductor position
Adjacent conductor
D/4 300A
Adjustment 50Hz
Full scale
Full scale
Adjustment 60Hz
Frequency
40Hz-5kHz
Deviation 50Hz-60Hz
Typical
Max
+/- 0.13% /°C
0.3%
2%
3%
2%
0.2%
0.3%
0.2%
0.3%
<+-1dB
<+-1dB
0.3%
1.4 Scale selection
The current sensors indicate the selected scale through the blue LED
located on the head of the same.
During the first 20 seconds after being turned on, the Wibeee Max
is in the scale selection period. The blue LED flashes quickly and
indicates the selected scale.
Verify that the clamps measure correctly once the equipment is
installed. If there is any incident, it is recommended to disconnect the
clamps from the equipment, wait 10 seconds and reconnect so that
they start correctly.
Press the RESET button during this period to select the desired scale:
- A single flash indicates that the 350-A scale has been
selected.
- A double flash indicates that the 700-A scale has
been selected.
Once the scale selection period has ended, rapid flashing is
deactivated, and the blue LED periodically indicates the selected
scale.