Important Safety Instructions
SAVE THESE INSTRUCTIONS
This manual contains important instructions that should be followed during the installation,
operation and storage of this product. Failure to heed these warnings may affect the warranty.
UPS Location Warnings
• Use caution when lifting the UPS. Because of the considerable weight of all rackmount UPS
systems, at least two people should assist in lifting and installing them.
• Install the UPS indoors, away from excess moisture or heat, dust or direct sunlight.
• For best performance, the ambient temperature near the UPS should be between 0° C and 40° C
(between 32° F and 104° F).
• Leave adequate space around all sides of the UPS for proper ventilation. Do not obstruct its vents
or fan openings.
• When mounting the UPS system in a tower orientation, make sure the LCD Screen panel is at the
top of the UPS, not at the bottom.
• Do not mount unit with its front or rear panel facing down (at any angle). Mounting in this manner
will seriously inhibit the unit's internal cooling, eventually causing product damage not covered
under warranty.
• Operating Temperature: 0°C to 40°C
• Storage Temperature: -15°C to 45°C
• Humidity: 0% to 90% R.H.
• Operating Altitude: 0 m to 2,000 m
• Storage Altitude: 0 m to 3,000 m
• Pollution: PD2
• Over-Voltage Category: II for normal mode, I for stored energy mode
UPS Connection Warnings
• The UPS contains its own energy source (battery). The output terminals may be live even when
the UPS is not connected to an AC supply.
• Connect the UPS to a properly grounded AC power outlet. Do not modify the UPS's plug in a way
that would eliminate the UPS's connection to ground. Do not use adapters that eliminate the
UPS's connection to ground.
• The power outlet that supplies the UPS should be installed near the UPS and be easily
accessible.
• Do not plug the UPS into itself; this will damage the UPS and void your warranty.
• If you are connecting the UPS to a motor-powered AC generator, the generator must provide
filtered, frequency-regulated computer-grade output. Connecting the UPS to a generator will void
its Ultimate Lifetime Insurance.
• For use on a TN power distribution system of input power supply. The UPS stored energy output
device provided a TN power system.