Connection with separate pipes
C
fig. 23- Examples of connection with separate pipes (
Table. 4 - Typology
Type
Description
C1X
Wall horizontal exhaust and intake. The inlet/outlet terminals must be concentric or close enough to be undergo similar wind con-
ditions (within 50 cm)
C3X
Roof vertical exhaust and intake. Inlet/outlet terminals like for C12
C5X
Wall or roof exhaust and intake separate or in any case in areas with different pressures. The exhaust and intake must not be
positioned on opposite walls.
C6X
Intake and exhaust with separately certified pipes (EN 1856/1)
B2X
Intake from installation room and wall or roof exhaust
IMPORTANT - THE ROOM MUST BE PROVIDED WITH APPROPRIATE VENTILATION
For the connection of separate ducts, fit the unit with the following starting accessory:
Before installation, make sure the maximum permissible length has not been exceeded, by means of a simple calculation:
1. Establish the layout of the system of split flues, including accessories and outlet terminals.
2. Consult table 6 and identify the losses in m
position.
3. Check that the sum total of losses is less than or equal to the maximum permissible length in table 5.
Table. 5- Max. length separate ducts
Max. permissible length
164
5x
80
cod. 041082X0
fig. 24- Starting accessory for separate ducts
(equivalent meters) of every component, according to the installation
eq
70 m
eq
cod. 3541N270 - Rev. 02 - 11/2017
BLUEHELIX TECH RRT 34 C
B
2x
= Air /
100
80
60
C
1x
= Fumes)
EN