Descargar Imprimir esta página

Ferroli BLUEHELIX TECH RRT 34 C Instrucciones De Uso, Instalación Y Mantenimiento página 190

Publicidad

Idiomas disponibles

Idiomas disponibles

3.4 Troubleshooting
Diagnostics
LCD Off
Make sure that the card is powered: using a digital multimeter, check for the
presence of supply voltage.
In case of no voltage, check the wiring.
If the voltage is sufficient ( Range 195 – 253 Vac ), check the fuse
(3.15AL@230VAC). The fuse is on the card. To reach it, see fig. 19 and fig. 51.
LCD On
In case of operating problems or trouble, the display flashes and the fault identification code appears
There are faults that cause permanent shutdowns (marked with the letter "A"): to restore operation it is sufficient to press
the reset button (detail 6 - fig. 1) for 1 second or use the RESET on the remote timer control (optional) if installed; if the
boiler does not restart, it is necessary to, firstly, eliminate the fault.
Other faults cause temporary shutdowns (marked with the letter "F") which are automatically reset as soon as the value
returns within the boiler's normal working range.
190
BLUEHELIX TECH RRT 34 C
cod. 3541N270 - Rev. 02 - 11/2017
fig. 51- Fuse housing
EN

Publicidad

loading

Este manual también es adecuado para:

0t3b3awa