The first time the unit receives the power supply, it will enter into ASSISTANT
mode. The display will show the message In{ flashing at 0.
The buttons  and  change the value, the SET button accepts the
value and moves on to the next step.
Step 1:
Select the most suitable InI option based on the type of installation to be carried out and press SET.
The available options will be shown in the following table:
Type of installation
InI
Control of
the compressor
Demo mode: it displays the temperature but does not regulate the temperature
0
No
1
Yes
2
Yes
3
No
4
Yes
5
Yes
6
Yes
7
Yes
8
If options 2, 5 or 7 are chosen, check the configuration of parameter I11 according to the pressure switch
type used.
Step 2:
Define the type of refrigerant gas used.
u02=0
R404A
u02=3
R407F
u02=6
R513A
u02=9
R290
u02=12 R1234ze u02=13
u02=15
R407C
u02=18
R454C
u02=21
R515B
u02=24
R454A
Pump
Vent.
Defrost
Down
Evap.
No
Electric
Yes
Electric
No
Electric
No
Air
Yes
Air
No
Air
Yes
Hot gas
No
Hot gas
u02=1
R134A
u02=2
u02=4
R410A
u02=5
u02=7
R744
u02=8
u02=10
R32
u02=11
R23
u02=14
u02=16
R1234yf
u02=17
u02=19
R455A
u02=20
u02=22
u02=23
R452A
22
1
Parameters
Pd o00 I00 I10 I11 I20 I21 d1 D7 F3
Yes
0
0
2
0
0
Yes
1
1
2
7
1
Yes
0
1
2
0
0
Yes
0
0
1
0
0
Yes
1
1
1
7
1
Yes
0
1
1
0
0
Yes
1
1
2
7
1
Yes
0
1
2
0
0
2
R407A
R450A
R449A
R448A
R717
R22
R507A
R452B
3516526A41 Ed. 02
 /  / SET
0
0 20 0
0
0
0 20 0
0
0
0 20 0
0
0
0 20 1
1
0
0 20 1
1
0
0 20 1
1
7
1
5
2
0
7
1
5
2
0
 /  / SET