3. Installation and Setup
3.7 Dual AC Input Installation
Dual AC Input UPS (or suffix "KXD") models are defaulted to a Single AC Input configuration via the placement of three shorting jumpers
between AC Input 1 and AC Input 2. If you desire to operate the "KXD" models in a dual AC configuration, remove these three jumpers,
and wire AC input 1 and AC Input 2 accordingly.
INPUT 2~
OUTPUT~
INPUT~
R
S
T
N
R
S
T
N
R
S
30-40K Model
INPUT BREAKER
ON
OFF
INPUT 2 BREAKER
ON
OFF
MAINTENANCE SWITCH
T
N
Jumpers on "KXD" dual-AC input models.
Note: Input neutrals are tied together internally.