The subsequent application of a non-conductive coating with a thickness of > 0.2mm on the external surface prohibits its use
in environments with potentially explosive atmospheres where group IIC Gases are present. The thickness of the coating must
be < 2mm for group IIB.
For group III it is necessary to take appropriate precautions to prevent the accumulation of electrostatic charges (e.g. cleaning
with an antistatic cloth, etc.).
3.4 - GENERIC EXAMPLE OF AN INSTALLATION
1. M16/RMOX N.A. Manual reset solenoid valve
2. SM jerk ON/OFF valve
3. FM gas filter
4. OPSO series MVB/1 MAX shut off valve
5. RG/2MC pressure regulator
10
1
4.0 - MANUAL RESET
To reset the solenoid valve:
• Make sure the valve is NOT electrically powered;
• Close the flow downstream of the solenoid valve in order to balance the pressure between upstream and downstream when opening;
• Push the reset handgrip (1) and wait a few seconds for the pressure upstream and downstream of the valve to stabilise;
• After balancing the pressures, pull the reset knob (1) until it connects.
• To close maually the solenoid valve (only M16/RMOCX N.A. versions), push the closing push button (12).
• The red label under the manual reset (1), if visible, shows that the valve is closed.
5.0 - FIRST START-UP
• Before start-up make sure that all of the instructions on the rating plate, including the direction of flow, are observed;
• After having gradually pressurized the system, check the seal and operation of the solenoid valve, electrically
powering / disconnecting it.
IMPORTANT NOTE: Do not use the connector as a switch to close the solenoid valve.
• Make sure the solenoid valve is closed by electrically connecting it.
5.1 - RECOMMENDED PERIODIC CHECKS
• Check tightness of the flanged/threaded connections on the system;
• Check tightness and operation of the solenoid valve;
• Clean the product regularly to prevent dust from building up;
M16/RMOX N.A. - M16/RMOCX N.A.
All manuals and user guides at all-guides.com
8
9
2
6. MVSP/1 relief valve
7. Pressure gauge and relative button
8. Gas detector
9. SM remote jerk ON/OFF valve lever control
10. Expansion joint/anti-vibration mount
7
3
4
12
Madas Technical Manual - 3|3.1bX - REV. 0 of 1t
6
7
5
discharge
in open air
Aug 2019