4.5
Technical specifications
Parameter
General specifications
Dimensions (W x H x D)
Weight
Housing material
Remote measurement
Measuring range (tank height)
Movement
Measuring accuracy
Indication
Operating temperature range
Ambient
Storage
Vertical line (wetted)
Material
Product description
Value
145 x 135 x 65 mm
400 g
Shock-resistant, impact-resistant
plastic
Up to 50 m
0/3000 mm "Unitel"
0/2500 mm "Unitel for water"
Linear capsule element with over-
pressure device
±3 % of full scale value
Standard: 0-100 % liquid level for rec-
tangular and cylindrical horizontal
tanks
-5/+55 °C
-5/+55 °C
The vertical line must consist of a
material that is neutral with regard to
the medium.
For example, for fuel oil EL, diesel fuel
and FAME: Pneumofix line (PVC),
copper pipe or oil-resistant Perbunan-
N hose with weight as spacer
EN
10
Unitel