ATTENTION: FOR ACTIVATION AIR RECIRCULATION (PAGE 27)
SCENARIO 1 - CON RICICLO D'ARIA ABILITATO
SCENARIO 1 - WITH AIR RECIRCULATION ENABLED
CHA = APERTURA
RICICLO D'ARIA
AIR RECIRCULATION OPENING
Opening force adjustment
P1 Press and hold the SET button, the display shows "P1".
P5 Press the UP button four times to display "P5".
Press the SET button again to display the current value. Press UP to increase the force by one level or press DOWN to decrease by one level.
F9
The max. level is "F9", the min. is "F1". The default setting is "F5".
F1
-- Press SET to confirm. The display shows "--".
Closing force adjustment
P1 Press and hold the SET button, the display shows "P1".
P2 Press the UP button again to display "P2".
Press the SET button again to display the current value. Press UP to increase the force by one level or press DOWN to decrease by one level.
F9
The max. level is "F9", the min. is "F1". The default setting is "F5".
F1
-- Press SET to confirm. The display shows "--".
Photocells
P1 Press and hold the SET button, the display shows "P1".
P3 Press the UP button twice to display "P3".
Press the SET button to display the current value. Press the UP button once to display "H1", the photocells are enabled. Press the DOWN button
H0
once to display "H0", the photocells are disabled. Press SET to confirm and exit.
H1
H0 If the photocell beam device is not used, make sure that "H0" is displayed, to close the function.
ON/OFF automatic closing
P1 Press and hold the SET button, the display shows "P1".
P4 Press the UP button three times to display "P4".
Press the SET button to display the current value. Press the UP button to increase the pause time for automatic re-closing or press the DOWN
B0
button to decrease the pause time for automatic re-closing. The maximum time is "B9" and the minimum time is "B1"; setting "b0" disables
B9
automatic reclosing. Press SET to confirm.
The default setting is "B0", automatic reclosing disabled. With a setting other than b0, the automatic reclosing function is activated when the
B0
door reaches full opening.
Automatic reclosing time
LED
B0
TIME
Reclosure disabled
(SEC.)
N.B.: Automatic closing does not work if the photocells are in alarm, or not installed and not disabled in parameter
Automatic reclosure after photocell activation
P1 Press and hold SET, the display shows "P1".
P0 Press DOWN once to display "P0".
Press SET to display the current value. Press UP to increase the automatic reclose time after photocell activation or press DOWN to decrease
the reclose time after photocell activation. The maximum time is "10" (seconds), the minimum is "01" (seconds); setting "00" disables automa-
00-10
tic reclosing after photocell activation. Press SET to confirm.
The default setting is '00', automatic reclosing disabled. With a setting other than '00', the automatic reclosing function is activated after the
00
activation of the photocells.
Condominium function
P1 Press and hold the SET button, the display shows "P1".
P6 Press the UP button five times to display "P6".
DISPLAY SPENTO
DISPLAY OFF
CHB = APERTURA / CHIUSURA PORTONE
OPENING / CLOSING DOOR
+
CHIUSURA RICICLO D'ARIA
AIR RECIRCULATION CLOSING
B1
B2
B3
10
20
30
RILASCIARE
RELEASE
SCENARIO 2 - CON RICICLO D'ARIA DISABILITATO
SCENARIO 2 - WITH AIR RECIRCULATION DISABLED
B4
B5
B6
40
50
60
P3 (H0)
S
U
-
.
.
CHB = APERTURA / CHIUSURA PORTONE
OPENING / CLOSING DOOR
B7
B8
90
120
-
.
.
B9
180
23